R.C.S.A. § 29-320-4a
Connecticut Supplement to NFPA 30A-1996 (Repealed)
Cite as Conn. Agencies Regs. § 29-320-4a
The National Fire Protection Association, Inc., NFPA 30A-1993, Automotive and Marine
Service Stations Code, is amended to meet the needs of Connecticut as follows:
CHAPTER 1 GENERAL PROVISIONS
(Amd) 1-2. Add or amend the following new definitions as appropriate:
Public Service Stations
Liquid motor fuel dispensing facilities open to the general motoring or boating public
with at least one attendant on duty while the station is open for business to store
and dispense liquids into the fuel tanks of motor vehicles or self propelled water
crafts (boats).
CHAPTER 2 STORAGE
(Add) 2-4.1.2. Aboveground tanks storing Class I liquids at automotive and marine
service stations shall be fire resistant tanks (see Section 2-4.5).
(Amd) 9-3.4. The provisions of Section 2-1.1 shall not prohibit the dispensing of
diesel motor fuel liquids in the open from a tank vehicle to a motor vehicle located
at commercial, industrial, governmental, or manufacturing establishments, and intended
for fueling vehicles used in connection with their businesses. Such dispensing may
be permitted provided:
(a) An inspection of the premises and operations has been made and approval granted by
the authority having jurisdiction;
(b) The tank vehicle complies with the requirements covered in NFPA 385, "Standard for
Tank Vehicles for Flammable and Combustible Liquids;"
(c) The dispensing hose does not exceed 50 ft (15m) in length;
(d) The dispensing nozzle is a listed automatic-closing type without a latch-open device;
(e) Nighttime deliveries shall only be made in adequately lighted areas;
(f) The tank vehicle flasher lights shall be in operation while dispensing;
(g) Fuel expansion space shall be left in each fuel tank to prevent overflow in the event
of temperature increase; and
(h) Written emergency procedures in the event of a spill or fire shall be conspicuously
posted at the dispensing area.
(Del) 9-3.5. Delete Section
(Amd) 9-4. Public Service Stations.
(Amd) 9-4.7. The dispensing area shall at all times be in clear view of the attendant.
The placing or allowing of any impairment of the view of the attendant shall be prohibited.
The use of a closed circuit television camera system is authorized to supplement the
attendant's view of the dispensing area. However, the use of such a closed circuit
television camera system shall require the approval of the local fire marshal prior
to such installation or use. The attendant shall at all times be able to communicate
by voice with persons in the dispensing area.
(Add) 9-4.8. Dispensing liquids at a public service station without an attendant present
is prohibited.
(Amd) 9-5. Unattended Self-Service at Fleet Vehicle Service Stations.
(Amd) 9-5.1. If an attendant is present at the dispensing facility, he or she shall
comply with the provisions of Section 9-4.
(Add) 9-5.1.1. When a person or employee of a company, fleet, commercial, industrial,
governmental or manufacturing establishment fuels a motor vehicle used in connection
with such businesses at an unattended fleet vehicle service station not owned or operated
by said person(s), the owner of the fleet vehicle service station shall be responsible
for training the person(s) using the facility. Evidence of such training shall be
documented and available for inspection.
The training shall include as a minimum:
(a) The proper operation of the dispensing equipment;
(b) The location and operation of emergency remote system shutoff(s); and
(c) Emergency response procedures to follow in the event of leak, discharge or fire
involving flammable or combustible liquids.
(Add) 9-5.1.2. A fleet vehicle service station dispensing area shall be suitably illuminated
by a reliable light source when in use.
(Amd) 9-9. Signs. Warning signs with the words "STOP MOTOR," "NO SMOKING" and "NO
OPEN FLAMES PERMITTED" in English at least 1 inch in height with a contrasting margin
shall be posted at all dispensing locations. The location of warning signs shall be
based on local conditions but shall be visible and legible from the point of liquid
transfer into the motor vehicle.
(Add) 9-10. Markings Of Dispenser Devices When Gaseous Motor Fuels Are Also Dispensed
As Motor Fuels.
(Add) 9-10.1. Warning signs identifying the type of motor fuel shall be posted at
all dispensing devices where both liquid and gaseous motor fuels are dispensed into
the fuel tanks of motor vehicles. Gaseous motor fuels include compressed natural gas
(CNG), liquefied natural gas (LNG) and liquefied petroleum gas (LPG).
Each warning sign shall be at least 3 feet above adjacent ground level and identify
the fuel in English in letters at least 3 1/2 inches in height with a contrasting
color margin. The name of the fuel shall not be abbreviated. The contrasting margin
shall be at least 2 inches from said letters. The warning signs shall be marked as
follows:
(a) The common name of a flammable liquid, such as "Gasoline" or "GASOLINE," shall
appear in white letters with a red background.
(b) The common name of a combustible liquid, such as "Diesel Fuel" or "DIESEL FUEL"
or "Kerosene" or "KEROSENE," shall appear in white letters with a green background.
(c) "Compressed Natural Gas" or "COMPRESSED NATURAL GAS," shall appear in black letters
with a yellow background.
(d) "Liquefied Natural Gas" or "LIQUEFIED NATURAL GAS," shall appear in black letters
with a yellow background.
(e) "Liquefied Petroleum Gas" or "LIQUEFIED PETROLEUM GAS" or "Propane" or "PROPANE,"
shall be centered in black letters and appear with a yellow background.