(a) Liquefied natural gas (LNG) storage facilities.
Liquefied natural gas (LNG) storage facilities shall have a protective enclosure for
aboveground components and a security system with controlled access designed to minimize
entry by unauthorized persons. The protective enclosure shall be illuminated and include
a non-combustible peripheral fence, building walls or natural barriers and be a minimum
of six feet in height, topped by a tamper-resistant system to discourage unlawful
entry or trespass. The tamper-resistant system shall consist of at least three strands
of barbed wire or other material sufficient to protect the facility. Peripheral fences,
building walls, or natural barriers in excess of 10 feet in height shall not require
a tamper-resistant material or system. The protective enclosure shall include major
aboveground facility components, such as:
(1) Liquefied natural gas containers;
(2) outdoor aboveground process equipment areas, including fill station(s); and
(3) on-shore loading and unloading equipment.
(b) Liquefied Petroleum Gas (LP-GAS) Storage Facilities.
(1) Liquefied Petroleum Gas (LP-GAS) Storage Facilities storing more than 4,000 gallons
aggregate water capacity.
Liquefied petroleum gas (LP-GAS) storage facilities storing more than 4,000 gallons
aggregate water capacity shall have a protective enclosure for aboveground components
and a security system with controlled access designed to minimize entry by unauthorized
persons. The protective enclosure shall be illuminated if operated during the hours
of darkness and include a non-combustible peripheral fence, building walls or natural
barriers and be a minimum of six feet in height and topped by a tamper-resistant system
to discourage unlawful entry or trespass. The tamper-resistant system shall consist
of at least three strands of barbed wire or other material sufficient to protect the
facility. Peripheral fences, building walls, or natural barriers in excess of 10 feet
in height shall not require a tamper-resistant material or system. The protective
enclosure shall include major aboveground facility components, such as:
(A) Liquefied petroleum gas containers;
(B) outdoor process equipment areas; and
(C) on-shore loading and unloading equipment.
(2) Liquefied petroleum gas (LP-GAS) storage facilities storing 4,000 gallons or less
aggregate water capacity and facilities transferring liquid LP-Gas into a building
piping system or another container of any size other than the motor vehicle fuel container.
Liquefied petroleum gas (LP-GAS) storage facilities storing 4,000 gallons or less
aggregate water capacity and facilities transferring liquid LP-Gas into a building
piping system or another container of any size other than the motor vehicle fuel container
shall be protected with an enclosure with controlled access, which shall be designed
to minimize entry by unauthorized persons and intruders, including a non-combustible
peripheral fence, building walls or natural barriers a minimum of six feet in height
to promote security of the facility. The protective enclosure shall include major
facility components, such as:
(A) Liquefied petroleum gas aboveground containers; and
(B) outdoor process equipment areas, including remote transfer points.
(3) Liquefied petroleum gas (LP-GAS) storage facilities storing more than 2,000 gallons
and up to and including 4,000 gallons aggregate water capacity aboveground and facilities
where liquefied petroleum gas in the vapor phase is used to supply LP-GAS vapor at
consumer sites, including but not limited to home(s) or residence(s), commercial or
industrial buildings.
Liquefied petroleum gas (LP-GAS) storage facilities storing more than 2,000 gallons
and up to and including 4,000 gallons aggregate water capacity aboveground, and facilities
where liquefied petroleum gas in the vapor phase is used to supply LP-GAS vapor at
consumer sites, including but not limited to home(s) or residence(s), commercial or
industrial buildings, shall be protected with an enclosure with controlled access,
which shall be designed to minimize entry by unauthorized persons and intruders, and
include a non-combustible peripheral fence, building walls, or natural barriers a
minimum of six feet in height to promote security of the facility. The protective
enclosure shall include major facility components such as:
(A) Liquefied petroleum gas aboveground containers; and
(B) outdoor process equipment areas, including remote transfer points.
(4) Liquefied petroleum gas (LP-Gas) storage facilities storing containers 2,000 gallons
aggregate water capacity or less.
Liquefied petroleum gas (LP-Gas) storage facilities storing containers 2,000 gallons
aggregate water capacity or less used to supply LP-GAS at consumer sites, including
but not limited to a home or residence, commercial or industrial building, do not
require protection with an enclosure.
(c) The protective enclosures for liquefied natural gas (LNG) and liquefied petroleum
gas (LP-GAS) storage facilities may be met by either one continuous enclosure or several
independent enclosures. When the enclosed area exceeds 1,250 square feet, not less
than two exit gates or doors located as remote as practical from each other shall
be provided for rapid escape of personnel in the event of an emergency.
(d) The presence of such protective enclosures shall not create significant hazards such
as pocketing of liquefied natural gas (LNG) or liquefied petroleum gas (LP-GAS), interference
with application of cooling water by fire departments, redirection of flames against
containers and impeding egress of personnel in an emergency.
(e) Lockable metal cabinets housing the dispensing controls for liquefied petroleum gas
(LP-Gas) storage facilities do not require protection with an enclosure.