R.C.S.A. § 29-349-340
Sprinklers, hydrants may be waived
Cite as Conn. Agencies Regs. § 29-349-340
The requirements for automatic sprinklers, water supplies and fire hydrants set forth in this Code may be waived by the State Fire Marshal when storage facilities are located in remote areas.
Table of Recommended Separation Distances of Ammonium Nitrate and Blasting Agents from Explosives or Blasting Agents (Notes 1, 6)**1
Minimum Separation
Distance of
Receptor When
Barricaded
Minimum
Thickness
of Artificial
Barricades
Donor Weight
(Note 2)
(Feet)
(Note 5)
(Inches)
Pounds
over
Pounds
not over
Ammonium
Nitrate
Blasting
Agent
100
3
11
12
100
300
4
14
12
300
600
5
18
12
600
1,000
6
22
12
1,000
1,600
7
25
12
1,600
2,000
8
29
12
2,000
3,000
9
32
15
3,000
4,000
10
36
15
4,000
6,000
11
40
15
6,000
8,000
12
43
20
8,000
10,000
13
47
20
10,000
12,000
14
50
20
12,000
16,000
15
54
25
16,000
20,000
16
58
25
20,000
25,000
18
65
25
25,000
30,000
19
68
30
30,000
35,000
20
72
30
35,000
40,000
21
76
30
40,000
45,000
22
79
35
45,000
50,000
23
83
35
50,000
55,000
24
86
35
55,000
60,000
25
90
35
60,000
70,000
26
94
40
70,000
80,000
28
101
40
80,000
90,000
30
108
40
90,000
100,000
32
115
40
100,000
120,000
34
122
50
120,000
140,000
37
133
50
140,000
160,000
40
144
50
160,000
180,000
44
158
50
180,000
200,000
48
173
50
200,000
220,000
52
187
60
220,000
250,000
56
202
60
250,000
275,000
60
216
60
275,000
300,000
64
230
60
1 ** This Table appears in Recommended Separation Distances of Ammonium Nitrate and Blasting Agents from Explosives or Blasting Agents, adopted as an NFPA Tentative Standard (No. 492-T) in 1967. For a discussion of the derivation of the Table and examples of how it is applied to actual storage situations, see No. 492-T.
NFPA 495 46 NOTE A46 New reference replaced reference to tentative recommendations in Information Circular 7988. New is as follows: \"Safety Recommendation for Sensitized Ammonium Nitrate Blasting Agents,\" Bureau of Mines, U.S. Department of Interior, Information Circular 8179, 1963.
NOTES TO TABLE OF RECOMMENDED SEPARATION AMMONIUM NITRATE AND BLASTING AGENTS FROM EXPLOSIVES OR BLASTING AGENTS
Note 1 — Recommended separation distances to prevent explosion of ammonium nitrate and ammonium nitrate based blasting agents by propagation from nearby stores of high explosive or blasting agents referred to in the Table as the \"donor.\" Ammonium nitrate, by itself, is not considered to be a donor when applying this Table. If stores of ammonium nitrate are located within the sympathetic detonation distance of explosives or blasting agents, one-half the mass of the ammonium nitrate should be included in the mass of the donor. These distances allow for the possibility of high velocity metal fragments from mixers, hoppers, truck bodies, sheet metal structures, metal containers, and the like, which may enclose the \"donor.\" These distances apply to the separation of stores only. The American Table of Distances shall be used in determining separation distances from inhabited buildings, passenger railways, and public highways.
Note 2 — When the ammonium nitrate and/or blasting agent is not barricaded, the distances shown in the Table shall be multiplied by six. Where storage is in bullet-resistant magazines recommended for explosives, or where the storage is protected by a bullet resistant wall, distances and barricade thickness in excess of those prescribed in the American Table of Distances are not required.
Note 3 — The distances in the Table apply to ammonium nitrate that passes the insensitivity test prescribed in the National Plant Food Institute;** and ammonium nitrate failing to pass said test shall be stored at separation distances determined by competent persons and approved by the State Fire Marshal’s Office.
Note 4 — These distances apply to nitro-carbo-nitrates and blasting agents which pass the insensitivity test prescribed in the DOT regulations.
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
* For construction of bullet-resistant magazines, see Chapter 3, NFPA 1967–68.
** Definition and Test Procedures of Ammonium Nitrate Fertilizer, National Plant Food Institute, November 1964.
Note 5 — Earth or sand dikes or enclosures filled with the prescribed minimum thickness of earth or sand are acceptable artificial barricades. Natural barricades, such as hills or timber of sufficient density that the surroundings exposures which require protection cannot be seen from the \"donor\" when the trees are bare of leaves, are also acceptable.
Note 6 — When the ammonium nitrate must be counted in determining the distances to be maintained from inhabited buildings, passenger railways and public highways, it may be counted at one-half its actual weight.