R.C.S.A. § 16-271-33
Odorization (Repealed)
Cite as Conn. Agencies Regs. § 16-271-33
All combustible gases transported or distributed by pipe line shall have a distinctive
odor of sufficient intensity so that a concentration of one-half of one per cent of
the gas in the air is readily perceptible to the normal or average olfactory senses
of a person coming from fresh uncontaminated air into a closed room containing one
part of the gas in one hundred ninety-nine parts of air. Whenever necessary to maintain
this level of intensity, a suitable odorant shall be added in accordance with the
following specifications:
(1) The odorant shall be harmless to humans, nontoxic and noncorrosive to steel, iron,
brass, copper and leather. It shall not be soluble in water to an extent greater than
two and one-half parts by weight of the odorant to one hundred parts by weight of
water;
(2) The products of combustion from the odorant shall be nontoxic to a person breathing
air containing these products of combustion and shall not be corrosive or harmful
to materials which normally would be exposed to such products of combustion;
(3) Equipment for introduction of the odorant into the gas shall be so designed and
so built as to avoid wide variation in the level of odor in the gas. The equipment
and facilities for handling the odorant shall be located where the escape of odorant
would not be a nuisance. Every company shall keep the commission informed of the type
of odorant used, the ratio of odorant to gas and the location of the odorization stations.