R.C.S.A. § 16-271-7
valves (Repealed)
Cite as Conn. Agencies Regs. § 16-271-7
Sectionalizing valves (block valves) shall be installed and maintained at strategic
points on the pipe lines system at an average of not less than one valve for each
five miles of pipe line in Class 4 locations and one valve for each eight miles in
Class 1, 2 or 3 locations with due regard to accessibiity and the possible necessity
for limiting a discharge of gas in the event of failure or an emergency. Such valves
shall be protected from damage and tampering. In all installations, an operating device
such as a suitable handwheel or wrench to open or close the valve shall be readily
accessible to authorized persons.