R.C.S.A. § 19-301-1
Test methods for determining labeling of self-pressurized dispensers
Cite as Conn. Agencies Regs. § 19-301-1
The type of warning statement required on self-pressurized dispensers shall be determined
by the performance of the contents of such dispensers when tested by Methods I, II
and III outlined below. When by Method I a flame projection exceeding 18 inches is
obtained with the valve open full, or flashback is obtained at any valve opening,
the container shall be labeled: "Warning (or Caution)- Do not use near fire or flame."
Materials yielding flash points below 80°F. by Method II shall be labeled "Warning
(or Caution)-Flammable. Do not use near heat or flame." When Method III shows any
significant propagation of flame through the vapor-air mixture in the open drum test,
or any explosion or burning of the vapor-air mixture sufficiently rapid to cause the
hinged cover to move in the closed drum test, the container shall be labeled: "Warning
(or Caution)-Do not use near heat or flame."
(a) Method I (Flame Projection Test).
(1) Apparatus. The apparatus consists of: (i) A base composed of a flat strip of wood or metal,
four inches wide and two feet long, cross-ruled at six-inch intervals; (ii) a ruler
thirty inches long, marked in inches, supported horizontally to one side of the base
and about six inches above it; and (iii) a plumber's candle, of such height that the
top third of its flame will be at the same level as the ruler, placed on the zero
marking of the base.
(2) Procedure. (This test requires two operators, one to manipulate the dispenser and the other
to take readings. Tests should be conducted in an area that is draft-free and capable
of ventilation after each test.) Light the candle. Let one observer hold the dispenser
being tested in such a position that it is six inches from the candle flame, with
its nozzle so pointed that any spray will pass at right angles through the top third
of the flame and extend lengthwise of the base and ruler. This observer shall operate
the spray device of the dispenser for fifteen to twenty seconds, while the other observer
records the horizontal extension of the candle flame. The test shall be repeated two
more times, and the three readings averaged.
(b) Method II (Modified Tagliabue Open Cup Test).
(1) . Apparatus. The apparatus consists of a standard Tagliabue open cup tester, a Tag gas flame testing
burner, a flash test thermometer, and a heat source.
(2) . Procedure. Place the container in an upright position and pierce its top with a fine-pointed
instrument. In a few moments, when most of the gas has escaped, enlarge the hole.
Finally, when there appears to be no further gas evolution, cut open the top of the
container and let it stand until the temperature of the contents reaches 60°F. Then
pour sufficient of the contents into the tester cup to fill it to the test line, immerse
a thermometer in the liquid, and apply heat at the rate of 2°F. per minute. As the
heating proceeds, apply the test flame at intervals until either a flame flashes completely
across the top of the cup or the height of the liquid has dropped one-fourth inch
below the test line. If flashing is obtained before the maximum permissible evaporation
has taken place, record as the flash point the temperature of the liquid at which
such flashing occurred.
(c) . Method III (Drum Test).
(1) . Apparatus. The apparatus consists of a fifty-five gallon open-head drum which has been modified
as follows: (i) A hinged cover, arranged so that it will open readily under a pressure
of five pounds, is fitted over the open head, (ii) three circular openings, one inch
in diameter, are bored through the base, about two inches from the edge, in such position
that when the drum is on its side one hole will be at the top, one at the bottom,
and one halfway down one side; (iii) a shutter capable of being readily opened and
closed is fitted over each of these holes; and (iv) a six-inch square opening is cut
through the center of the base and securely covered with a piece of safety glass.
(2) . Procedure. Lay the modified drum on its side out in the open, at a time when the temperature
is between 60° and 80°F. Stand a plumber's candle (or similar flame source) inside
the drum half way from each end. For the open drum test, proceed as follows: Fully
open the hinged cover, close all three shutters, light the candle, direct a spray
from the dispenser (valve fully open) for one minute into the upper half of the open
end of the drum and above the candle flame, and watch for propagation of the flame
through the vapor-air mixture away from the candle. For the closed drum test, proceed
as follows: (i) Light the candle, drop the hinged cover down so that it rests free
against the edge of the drum, open the top shutter on the other end, jet a spray from
the container being tested (valve fully open) into the drum through this opening for
one minute, and observe whether sufficient explosion or rapid burning of the vapor-air
mixture takes place to cause the hinged cover to move; (ii) after clearing the atmosphere
in the drum each time, repeat this test twice as before, except to spray in turn from
the side and bottom openings.