20 DCMR 5702
5702. NEW HAZARDOUS SUBSTANCE UST SYSTEMS
Cite as D.C. Mun. Regs. tit. 20, § 5702
5702 NEW HAZARDOUS SUBSTANCE UST SYSTEMS
5702.1 Each new hazardous substance UST shall be:
(a) Constructed of fiberglass-reinforced plastic, steel-fiberglass-reinforced plastic composite, or steel;
(b) If constructed of steel, cathodically protected in accordance with the requirements of § 5702.2; and
(c) Of three hundred sixty degree (360°) double-wall construction as set forth in § 5702.4.
5702.2 Each steel tank shall be cathodically protected by being coated with a suitable dielectric material, and:
(a) The field-installed cathodic protection systems shall be designed by a corrosion expert; and
(b) The impressed current cathodic protection systems shall be designed to allow determination of current operating status as required by § 5901.5.
5702.3 Each cathodic protection system shall be operated and maintained in accordance with § 5901.
5702.4 Double-walled tanks shall be designed, constructed, and installed in a manner that will:
(a) Contain a release from any portion of the inner tank within the outer wall until detected and removed;
(b) Detect the failure of the inner or outer wall;
Prevent the release of regulated substances to the environment at any time during the operational life of the UST; and
Check for evidence of a release at least every thirty (30) days.
5702.5 The codes of practice listed in §§ 5701.10(a) and (b) may be used to comply with § 5702.1
SOURCE: Final Rulemaking published at 40 DCR 7835 (November 12, 1993); as amended by Final Rulemaking published at 46 DCR 7699 (October 1, 1999); as amended by Final Rulemaking published at 67 DCR 1778 (February 21, 2020).