12-F DCMR 604
604. DESIGN OF BUILDING WATER DISTRIBUTION SYSTEM
Cite as D.C. Mun. Regs. tit. 12-F, § 604
604 DESIGN OF BUILDING WATER DISTRIBUTION SYSTEM
Strike Table 604.4 in the International Plumbing Code in its entirety and insert new Table 604.4 in the Plumbing Code in its place to read as follows:
TABLE 604.4
MAXIMUM FLOW RATES AND CONSUMPTION FOR
PLUMBING FIXTURES AND FIXTURE FITTINGS
PLUMBING FIXTURE
OR FIXTURE FITTING MAXIMUM FLOW RATE
OR QUANTITYb Lavatory and bar sink faucet, private 1.5 gpm at 60psi and WaterSense labeled Lavatory, public (metering) 0.25 gallon per metering cycle Lavatory, public
(other than metering) 0.5 gpm at 60 psi Bar sink faucet in other than dwelling units or hotel and hospital private rooms 2.2 gpm at 60 psi Shower heada 2.0 gpm at 80psi and WaterSense labeled Sink faucet, kitchen 2.2 gpm at 60 psi Urinal, flushing or non-water 0.5 gallon per flushing cycle and WaterSense labeled, or non-water urinals Water closet, public and remoted 1.6 gallons per flushing cycle Water closet (tank type)c 1.28 gallons per flushing cycle and WaterSense labeled Water closet, private flushometer type, or public and non-remote 1.28 gallons per flushing cycle
For SI: 1 gallon per minute = 3.785 L/m,
1 pound per square inch = 6.895 kPa
a. A hand-held shower spray is a shower head
b. Consumption tolerances shall be determined from referenced standards.
c. Dual Flush Toilets - The effective flush volume shall not exceed 1.28 gallons (4.8 liters). The effective flush volume is defined as the composite, average flush volume of two reduced flushes and one full flush. Flush volumes will be tested in accordance with ASME A112.19.2 and ASME A112.19.14.
d. A remote water closet is a water closet that is located not less than 30 feet (9144 mm) upstream of other drain line connections or fixtures and where less than 1.5 drainage fixture units are upstream of the drain line connection.
SOURCE: Final Rulemaking published at 61 DCR 3169 (March 28, 2014 – Part 2); as corrected by Errata Notice published at 61 DCR 5246 (May 23, 2014).
The District of Columbia Plumbing Code (2013), referred to as the “Plumbing Code,” consists of the 2012 edition of the International Plumbing Code as amended by the District of Columbia Plumbing Code Supplement (2013) (12 DCMR F). The International Plumbing Code is copyrighted by the International Code Council and therefore is not republished here. However, a copy of the text may be obtained at: http://publicecodes.cyberregs.com/icod/ipc/2012/index.htm?bu=IC-P-2012-000004&bu2=IC-P-2012-000019.
District of Columbia Municipal Regulations
Plumbing Code Supplement of 2013
12-F DCMR § 604