40 C.F.R. Table 2 to Subpart Cb of Part 60

Table 2 to Subpart C b of Part 60—Nitrogen Oxides Limits for Existing Designated Facilities Included in an Emissions Averaging Plan at a Municipal Waste Combustor Plant b

Last amended: 2016Year: 2026Length: 92 wordsOfficial source

Cite as 40 C.F.R. Table 2 to Subpart Cb of Part 60 (2026)

Municipal waste combustor technology Before April 28, 2009, nitrogen oxides emission limit (parts per million by volume) b On and after April 28, 2009, nitrogen oxides emission limit (parts per million by volume) a Mass burn waterwall 185 185 Mass burn rotary waterwall 220 190 Refuse-derived fuel combustor 230 230 Fluidized bed combustor 165 165 a Mass burn refractory municipal waste combustors and other MWC technologies not listed above may not be included in an emissions averaging plan. b Corrected to 7 percent oxygen, dry basis. [71 FR 27334, May 10, 2006]
40 C.F.R. Table 2 to Subpart Cb of Part 60: Table 2 to Subpart C b of Part 60—Nitrogen Oxides Limits for Existing Designated Facilities Included in an Emissions Averaging Plan at a Municipal Waste Combustor Plant b | Justis AI