40 C.F.R. Table 2 to Subpart VVVV

Emission Limitations for New Large Municipal Waste Combustors

Last amended: 2026Year: 2026Length: 166 wordsOfficial source

Cite as 40 C.F.R. Table 2 to Subpart VVVV (2026)

For the air pollutant If your affected facility is a new large municipal waste combustor, you must meet this emission limit, corrected to 7 percent oxygen a Particulate matter 5.1 mg/dscm. Opacity 10 percent opacity (6-minute block average). Cadmium 2.3 ug/dscm. Lead 23 ug/dscm. Mercury 32 ug/dscm or 85 percent reduction by weight. Sulfur dioxide 14 parts per million by volume dry basis or 79 percent reduction by weight or volume (daily 24-hour geometric average). Hydrogen chloride 7.2 parts per million by volume dry basis or 98 percent reduction by weight or volume. Dioxins/furans 11 nanograms per dry standard cubic meter (total mass). Nitrogen oxides 50 parts per million by volume dry basis (daily 24-hour arithmetic average). a Measured at the combustor outlet in conjunction with a measurement of oxygen concentration. CEMS data during warmup, startup, and shutdown, as defined in this subpart, are not corrected to 7 percent oxygen, and are used as measured. The averaging times are specified in greater detail in § 60.5940.
Cross-references to the CFR
60.5940.