40 C.F.R. § 76.7

Revised NO X emission limitations for Group 1, Phase II boilers.

Last amended: 2016Year: 2026Length: 141 wordsSubsections: 1Official source

Cite as 40 C.F.R. § 76.7 (2026)

(a) Beginning January 1, 2000, the owner or operator of a Group 1, Phase II coal-fired utility unit with a tangentially fired boiler or a dry bottom wall-fired boiler shall not discharge, or allow to be discharged, emissions of NO X to the atmosphere in excess of the following limits, except as provided in §§ 76.8, 76.10, or 76.11: (1) 0.40 lb/mmBtu of heat input on an annual average basis for tangentially fired boilers. (2) 0.46 lb/ mmBtu of heat input on an annual average basis for dry bottom wall-fired boilers (other than units applying cell burner technology). (b) The owner or operator shall determine the annual average NO X emission rate, in lb/mmBtu, using the methods and procedures specified in part 75 of this chapter. [60 FR 18761, Apr. 13, 1995, as amended at 61 FR 67163, Dec. 19, 1996]
Cross-references to the CFR
76.8
40 C.F.R. § 76.7: Revised NO X emission limitations for Group 1, Phase II boilers. | Justis AI