46 C.F.R. § 108.437

Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.

Last amended: 2016Year: 2026Length: 79 wordsSubsections: 3Official source

Cite as 46 C.F.R. § 108.437 (2026)

(a) The minimum pipe size for the initial charge must meet table 108.441 and the discharge of the required amount of CO 2 must be completed within 2 minutes. (b) The minimum pipe size for the delayed discharge must be at least 1.25 centimeters ( 1/2 inch) standard pipe. (c) The pipe used for the initial discharge must not be used for the delayed discharge, except systems having a volume of less than 57 cubic meters (2,000 cubic feet).