46 C.F.R. § 111.05-19

Tank vessels; grounded distribution systems.

Last amended: 2016Year: 2026Length: 85 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 111.05-19 (2026)

(a) If the voltage of a distribution system is less than 1,000 volts, line to line, a tank vessel must not have a grounded distribution system. (b) If the voltage of a distribution system on a tank vessel is 1,000 volts or greater, line to line, and the distribution system is grounded (including high-impedance grounding), any resulting current must not flow through a hazardous (classified) location. [CGD 94-108, 61 FR 28276, June 4, 1996, as amended at 62 FR 23907, May 1, 1997] Ground Detection