46 C.F.R. § 111.12-9

Generator cables.

Last amended: 2016Year: 2026Length: 49 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 111.12-9 (2026)

(a) The current-carrying capacity of generator cables must not be: (1) Less than 115 percent of the continuous generator rating; or (2) Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating. (b) Generator cables must not be in the bilges.