46 C.F.R. § 111.97-9

Overcurrent protection.

Last amended: 2016Year: 2026Length: 81 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 111.97-9 (2026)

Overcurrent devices must be arranged to isolate a fault with as little disruption of the system as possible. The relationship between the load and the rating or setting of overcurrent devices must meet the following: (a) The rating or setting of each feeder overcurrent device must be not less than 200 percent of its maximum load. (b) The rating or setting of a branch circuit overcurrent device must be not more than 25 percent of that of the feeder overcurrent device.