46 C.F.R. § 112.20-5

Failure of power from the normal source or final emergency power source.

Last amended: 2016Year: 2026Length: 90 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 112.20-5 (2026)

(a) If there is a reduction of potential of the normal source by 15 to 40 percent, the loads under § 112.15-1 must be automatically supplied from the temporary emergency power source. (b) For systems in which a reduction of frequency of the normal source or final emergency power source adversely affects the emergency system and emergency loads, there must be means to transfer the loads under § 112.15-1 to the temporary emergency power source upon a reduction in the frequency of the normal source or final emergency power source.