46 C.F.R. § 112.55-15

Capacity of storage batteries.

Last amended: 2016Year: 2026Length: 103 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 112.55-15 (2026)

(a) A storage battery for an emergency lighting and power system must have the capacity— (1) To close all watertight doors two times; (2) To open all watertight doors once; and (3) To carry the remaining emergency loads continuously for the time prescribed in § 112.05-5(a), table 112.05-5(a). (b) At the end of the time specified in paragraph (a) of this section, the potential of the storage battery must be at least 88 percent of the standard voltage. [CGD 74-125A, 47 FR 15267, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28288, June 4, 1996; 61 FR 39695, July 30, 1996]