46 C.F.R. § 113.20-3

Connection boxes.

Last amended: 2023Year: 2026Length: 57 wordsOfficial source

Cite as 46 C.F.R. § 113.20-3 (2026)

Each connection box and each switch enclosure in an automatic sprinkler system must be constructed in accordance with Type 4 or 4X of NEMA 250 or IP 56 of IEC 60529:2013 (both incorporated by reference; see 46 CFR 110.10-1) requirements. [USCG-2003-16630, 73 FR 65201, Oct. 31, 2008, as amended by USCG-2020-0075, 88 FR 16369, Mar. 16, 2023]
Cross-references to the CFR
46:110.10-1