46 C.F.R. § 119.530

Bilge high level alarms.

Last amended: 2016Year: 2026Length: 134 wordsSubsections: 2Official source

Cite as 46 C.F.R. § 119.530 (2026)

(a) Each vessel must be provided with a visual and audible alarm at the operating station to indicate a high water level in each of the following normally unmanned spaces: (1) A space with a through-hull fitting below the deepest load waterline, such as a lazarette; (2) A machinery space bilge, bilge well, shaft alley bilge, or other spaces subject to flooding from sea water piping within the space; and (3) A space with a non-watertight closure , such as a space with a non-watertight hatch on the main deck. (b) A visual indicator must be provided at the operating station to indicate when any automatic bilge pump is operating. [CGD 85-080, 61 FR 922, Jan. 10, 1996; 61 FR 20556, May 7, 1996, as amended by USCG-2014-0688, 79 FR 58283, Sept. 29, 2014]