46 C.F.R. § 143.230

Alarms and monitoring.

Last amended: 2016Year: 2026Length: 241 wordsSubsections: 3Official source

Cite as 46 C.F.R. § 143.230 (2026)

(a) Each towing vessel must have a reliable means to provide notification when an emergency condition exists or an essential system develops problems that require attention. The following alarms must be provided: (1) Main engine low lubricating oil pressure; (2) Main engine high cooling water temperature; (3) Auxiliary generator engine low lubricating oil pressure; (4) Auxiliary generator engine high cooling water temperature; (5) High bilge levels; (6) Low hydraulic steering fluid levels, if applicable; and (7) Low fuel level, if fitted with a day tank. (b) Alarms must: (1) Be visible and audible at each operating station. The alarm located at the operating station may be a summary alarm; if the alarm at the operating station is a summary alarm, the specific alarm condition must be indicated at the machinery or bilge location; (2) Have a means to test actuation at each operating station or have a continuous self-monitoring alarm system which actuates if an alarm point fails or becomes disabled; (3) Continue until they are acknowledged; and (4) Not interfere with night vision at the operating station. (c) The following systems must be equipped with gauges at the machinery location: (1) Main engine lubricating oil pressure and main engine RPM; (2) Main engine cooling water temperature; (3) Auxiliary generator engine lubricating oil pressure and auxiliary generator engine RPM; (4) Auxiliary generator engine cooling water temperature; and (5) Hydraulic steering fluid pressure, if the vessel is equipped with hydraulic steering systems.