46 C.F.R. § 161.002-6

Testing requirements.

Last amended: 2016Year: 2026Length: 393 wordsSubsections: 4Official source

Cite as 46 C.F.R. § 161.002-6 (2026)

(a) Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7. (b) Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1) as appropriate: (1) Control units—UL 864; (2) Heat detectors—UL 521; (3) Smoke detectors—UL 268; (4) Flame detectors—ANSI/FM 3260; (5) Audible alarms—UL 464 or UL 1480; (6) Visual alarms—UL 1971; and (7) Manual Signaling Boxes—UL 38. (c) All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1). Table 161.002-6( c )—Marine Environmental Testing Requirements IEC 60092-504 Environmental type test Category 1 Category 2 Category 3 All spaces not Category 2 or 3 Open deck or open to weather Spaces containing navigation or communication equipment 1—Visual inspection X X X 2—Functional test X X X 3—High voltage test X X X 4a—Power supply variations X X X 4b—Power supply failure X X X 5—Insulation resistance X X X 6—Cold with gradual temp. change X (5 °C) X (−25 °C) X (5 °C) 7—Dry heat with gradual temp. change X (55 °C) X (55 °C) X (55 °C) 8—Damp heat, cyclic X X X 9—Salt mist X 10—Vibration (sinusoidal) X X X 11b—Inclination, dynamic 1 X 1 X 1 X 13—Electrostatic discharge X X X 14—Electromagnetic field X X X 15—Conducted low frequency X X X 16(a)—Conducted radio frequency (3 V rms) X 16(b)—Conducted radio frequency (10 V rms) X X 17—Burst/fast transients X X X 18—Surge/slow transients X X X 19(a)—Radiated emission (general power) X 19(b)—Radiated emission (bridge and deck zone) X X 20(a)—Conducted emission (general power) X 20(b)—Conducted emission (bridge and deck zone) X X 1 This test only needs to be completed if the device is in a location with moving mechanical parts. (d) All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1) if the requirements exceed those of 46 CFR 111.01-9. Otherwise, 46 CFR 111.01-9 must be complied with. [USCG-2012-0196, 81 FR 48275, July 22, 2016]
Cross-references to the CFR
159.010161.002-129:1910.7.46:111.01-946:111.01-9.
46 C.F.R. § 161.002-6: Testing requirements. | Justis AI