46 C.F.R. § 169.559
Fire pumps.
Cite as 46 C.F.R. § 169.559 (2026)
(a) Each sailing school vessel must be equipped with fire pumps as required in Table 169.559(a).
Table 169.559(
a
)—Fire Pumps
Length
Exposed and partially protected water service
Protected water service
65 feet but less than 90 feet
1
1
0
90 feet but less than 120 feet
2
1
1
1
120 feet or greater
3
2
1
1
1
May be driven off a propulsion engine and may be used as a bilge pump.
2
Must be driven by a source of power independent of the propulsion engine and may be used as a bilge pump.
3
One pump may be driven off a propulsion unit and one pump may be used as a bilge pump. Pumps must be located in separate spaces.
(b) Fire pump capacity must be in accordance with the following:
Vessel length
Minimum capacity
Less than 90 ft
5.5 m
3
/hr (25 gpm).
90 feet but less than 120 ft
11.0 m
3
/hr (50 gpm).
Greater than 120 ft
14.3 m
3
/hr (66.6 gpm).
(c) Each fire pump must be fitted with a pressure gage on the discharge side of the pump.
(d) Each vessel must have a hand operated portable fire pump having a capacity of at least 1.1 m
3
/hr (5 gpm). This pump must be equipped with suction and discharge hose suitable for use in firefighting.