46 C.F.R. § 181.420

Pre-engineered fixed gas fire extinguishing systems.

Last amended: 2016Year: 2026Length: 147 wordsSubsections: 3Official source

Cite as 46 C.F.R. § 181.420 (2026)

(a) A pre-engineered fixed gas fire extinguishing system must: (1) Be approved by the Commandant; (2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector; (3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space; and (4) Be installed in accordance with the manufacturer's instructions. (b) A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station: (1) A light to indicate discharge; (2) An audible alarm that sounds upon discharge; and (3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section. (c) Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.