46 C.F.R. § 76.33-10

Location and spacing of accumulators.

Last amended: 2016Year: 2026Length: 84 wordsSubsections: 3Official source

Cite as 46 C.F.R. § 76.33-10 (2026)

(a) Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected. (b) No spot on the overhead of a protected space may be more than 40 feet from an accumulator. (c) Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening. [CGFR 65-50, 30 FR 16940, Dec. 30, 1965, as amended by USCG-2012-0196, 81 FR 48259, July 22, 2016]