46 C.F.R. § 98.30-37

Firefighting requirements.

Last amended: 2016Year: 2026Length: 195 wordsSubsections: 5Official source

Cite as 46 C.F.R. § 98.30-37 (2026)

No person may lift a portable tank on or off a vessel, or transfer a product with a flashpoint of less than 300 °F to or from a portable tank or IBC unless— (a) Water pressure is maintained on the firemain; (b) Firehoses, fitted with a Coast Guard-approved combination nozzle, are attached to each fire hydrant in the vicinity of the portable tanks; (c) Except as provided in § 98.30-39, fire extinguishers of a dry chemical type are— (1) Located to protect the deck area 10 feet in any horizontal direction from each portable tank and its associated cargo handling system; (2) Coast Guard approved; and (3) Capable of covering the deck area without being moved; (d) In a deck area of 500 square feet or less, there are two or more dry chemical fire extinguishers of 300 pounds or more total capacity of extinguishing agent; and (e) In a deck area of more than 500 square feet, there are three or more dry chemical fire extinguishers of 450 pounds or more total capacity of extinguishing agent. [CGD 73-172, 39 FR 22954, June 25, 1974, as amended by USCG-2011-0088, 78 FR 54787, Sept. 6, 2013]
Cross-references to the CFR
98.30-39