64E-5.1413, F.A.C.

64E-5.1413. Power Failures

Last amended: 1996Year: 2026Length: 72 wordsOfficial source

Cite as Fla. Admin. Code r. 64E-5.1413

(1) If electrical power at a panoramic irradiator is lost for longer than 10 seconds, the sources must return automatically to the shielded position. (2) The lock on the door of the radiation room of a panoramic irradiator must not be deactivated by a power failure. (3) During a power failure, the area around the pool of an irradiator shall not be entered without using an operable and calibrated radiation survey meter.
64E-5.1413, F.A.C.: 64E-5.1413. Power Failures | Justis AI