69A-43.0095, F.A.C.

69A-43.0095. Individually Annunciated at Panel

Last amended: 2001Year: 2026Length: 148 wordsOfficial source

Cite as Fla. Admin. Code r. 69A-43.0095

Single station smoke detectors which annunciate at a panel at a supervised location, where used, shall meet the following: (1) All means of interconnecting equipment, devices and/or appliances shall be monitored for the integrity of the conductors or equivalent so that the occurrence of a single open or a single ground trouble condition in the installation conductors and their restoration to normal shall be automatically signaled as โ€œtroubleโ€ at the panel in the supervised location. (2) Trouble signals shall be audible and distinctive from alarm signals, and shall comply with NFPA 72, Section 1-5.4.6, the edition as adopted in rule Chapter 69A-3, F.A.C. (3) The annunciator system shall have primary power supplied in accordance with NFPA 72, Section 1-5.2.4, the edition as adopted in rule Chapter 69A-3, F.A.C., and secondary power supplied in accordance with NFPA 72, Section 1-5.2.5, the edition as adopted in rule Chapter 69A-3, F.A.C.