UST SYSTEMS: DESIGN, CONSTRUCTION, AND INSTALLATION
§11-280.1-20
Performance standards for UST
systems.
(a)
In order to prevent releases due to
structural failure, corrosion, or spills and overfills
for as long as the UST system is used to store
regulated substances, owners and operators of UST
systems must meet all applicable requirements of this
subchapter. UST systems must meet the requirements of
this section as follows:
280.1-20
3 5 8 4
§11-280.1-20
(1)
UST systems installed after December 22,
1988, other than airport hydrant fuel
distribution systems and UST systems with
field-constructed tanks, must meet the
requirements of this section, except as
specified in subsection (g).
(2)
Airport hydrant fuel distribution systems
and UST systems with field-constructed tanks
installed on or after July 15, 2018 must
meet the requirements of this section.
(b)
Tanks. Each tank must be properly designed,
constructed, and installed, and any portion
underground that routinely contains product must be
protected from corrosion, in accordance with a code of
practice developed by a nationally recognized
association or independent testing laboratory as
specified below:
(1)
The tank is constructed of fiberglass
reinforced plastic; or
(2)
The tank is constructed of steel and
cathodically protected in the following
manner:
(A)
The tank is coated with a suitable
dielectric material;
(B)
Field-installed cathodic protection
systems are designed by a corrosion
expert;
(C)
Impressed current systems are designed
to allow determination of current
operating status as required in section
11-280.1-31(3); and
(D)
Cathodic protection systems are
operated and maintained in accordance
with section 11-280.1-31 or according
to guidelines established by the
department; or
(3)
The tank is constructed of steel and clad or
jacketed with a non-corrodible material; or
(4)
The tank is constructed of metal without
additional corrosion protection measures
provided that:
(A)
The tank is installed at a site that is
280.1-21
3 5 8 4
§11-280.1-20
determined by a corrosion expert not to
be corrosive enough to cause it to have
a release due to corrosion during its
operating life; and
(B)
Owners and operators maintain records
that demonstrate compliance with the
requirements of subparagraph (A) for
the remaining life of the tank; or
(5)
The tank construction and corrosion
protection are determined by the department
to be designed to prevent the release or
threatened release of any stored regulated
substance in a manner that is no less
protective of human health and the
environment than paragraphs (1) to (4).
(c)
Piping. The piping that routinely contains
regulated substances and is in contact with the ground
must be properly designed, constructed, installed, and
protected from corrosion in accordance with a code of
practice developed by a nationally recognized
association or independent testing laboratory as
specified below:
(1)
The piping is constructed of a non
corrodible material; or
(2)
The piping is constructed of steel and
cathodically protected in the following
manner:
(A)
The piping is coated with a suitable
dielectric material;
(B)
Field-installed cathodic protection
systems are designed by a corrosion
expert;
(C)
Impressed current systems are designed
to allow determination of current
operating status as required in section
11-280.1-31(3); and
(D)
Cathodic protection systems are
operated and maintained in accordance
with section 11-280.1-31 or guidelines
established by the department; or
(3)
The piping is constructed of metal without
additional corrosion protection measures
280.1-22
3 5 8 4
§11-280.1-20
provided that:
(A)
The piping is installed at a site that
is determined by a corrosion expert to
not be corrosive enough to cause it to
have a release due to corrosion during
its operating life; and
(B)
Owners and operators maintain records
that demonstrate compliance with the
requirements of subparagraph (A) for
the remaining life of the piping; or
(4)
The piping construction and corrosion
protection are determined by the department
to be designed to prevent the release or
threatened release of any stored regulated
substance in a manner that is no less
protective of human health and the
environment than the requirements in
paragraphs (1) to (3).
(d)
Spill and overfill prevention equipment.
(1)
Except as provided in paragraphs (2) and
(3), to prevent spilling and overfilling
associated with product transfer to the UST
system, owners and operators must use the
following spill and overfill prevention
equipment:
(A)
Spill prevention equipment that
will prevent release of product
to the environment when the
transfer hose is detached from
the fill pipe (for example, a
spill catchment basin); and
(B)
Overfill prevention equipment
that will:
(i)
Automatically shut off flow into
the tank when the tank is no more
than ninety-five percent full;
(ii)
Alert the transfer operator when
the tank is no more than ninety
percent full by restricting the
flow into the tank or triggering a
high-level alarm; or
(iii)
Restrict flow thirty minutes prior
280.1-23
3 5 8 4
◄
§11-280.1-20
to overfilling, alert the transfer
operator with a high-level alarm
one minute before overfilling, or
automatically shut off flow into
the tank so that none of the
fittings located on top of the
tank are exposed to product due to
overfilling.
(2)
Owners and operators are not required to use
the spill and overfill prevention equipment
specified in paragraph (1) if:
(Al
Alternative equipment is used
that is determined by the
department to be no less
protective of human health and
the environment than the
equipment specified in paragraph
(1) (A) or (B); or
(B)
The UST system is filled by
transfers of no more than twenty
five gallons at one time.
(3)
Flow restrictors used in vent lines may not
be used to comply with paragraph (1) (B) when
overfill prevention is installed or replaced
after July 15, 2018.
(4)
Overfill prevention methods that rely on the
use of alarms must have the alarms clearly
labeled "overfill alarmu and located where
the delivery person can clearly see and hear
the alarm in order to immediately stop
delivery of the product.
(5)
Spill and overfill prevention equipment must
be periodically tested or inspected in
accordance with section 11-280.1-35.
(e)
Installation. The UST system must be
properly installed in accordance with a code of
practice developed by a nationally recognized
association or independent testing laboratory and in
accordance with the manufacturer's instructions.
(f)
Certification of installation. All owners
and operators must ensure that one or more of the
following methods of certification, testing, or
280.1-24
0 5 8 4
§11-280.1-20
inspection is used to demonstrate compliance with
subsection (e) by providing a certification of
compliance on the "Certification of Underground
Storage Tank Installation" form prescribed by the
director and in accordance with section
11-280.1-325(d).
(1)
The installer has been certified by the tank
and piping manufacturers;
(2)
The installer has been certified or licensed
by the department;
(3)
The installation has been inspected and
certified by a licensed professional
engineer with education and experience in
UST system installation;
(4)
The installation has been inspected and
approved by the department;
(5)
All work listed in the manufacturer's
installation checklists has been completed
and the checklists maintained; or
(6)
The owner and operator have complied with
another method for ensuring compliance with
subsection (e) that is determined by the
department to be no less protective of human
health and the environment.
(g)
Secondary containment.
(1)
UST systems installed on or after August 9,
2013, other than airport hydrant fuel
distribution systems and UST systems with
field-constructed tanks, must be provided
with secondary containment that meets the
requirements of section 11-280.1-24, except
for suction piping that meets the
requirements of section 11-280.1-41 (b) (6).
(2)
Airport hydrant fuel distribution systems
and UST systems with field-constructed tanks
must be provided with secondary containment
that meets the requirements of section
11-280.1-24, except for:
(A)
Suction piping that meets the
requirements of section
11-280.1-4l(b) (6);
(B)
Piping associated with UST systems with
280.1-25
3 5 8 4
§11-280.1-20
field-constructed tanks with a capacity
greater than 50,000 gallons; and
(C)
Piping associated with airport hydrant
systems.
[Eff 7/15/18; comp 1/17/20;
am and comp 7/8/21; comp MAR212025
(Auth: HRS §§342L-3, 342L-32}
(Imp:
HRS §§3421-3, 342L-32)