HAR §11-280.1-25
HAR §11-280.1-25. Under-dispenser containment
Length: 752 wordsOfficial source
Cite as Haw. Code R. § 11-280.1-25
(a)
Dispenser systems installed on or after August 9,
2013, other than for airport hydrant fuel distribution
systems and UST systems with field-constructed tanks,
must have under-dispenser containment that meets the
requirements in subsection (c).
(b)
Dispenser systems installed on or after July
15, 2018 must have under-dispenser containment that
meets the requirements in subsection (c).
(c)
Under-dispenser containment required by
subsection (a) or (b) must:
(1)
Be liquid-tight on its sides, bottom, and at
any penetrations;
(2)
Be compatible with the substance conveyed by
the piping; and
(3)
Meet one of the following requirements:
(A)
Allow for visual inspection and access
to the components in the containment
system; or
(B)
Be monitored for leaks from the
dispenser system with a sensing device
that signals the operator of the
presence of regulated substances.
[Eff
7/15/18; comp 1/17/20; am and comp
280.1-28
· •
3 5 8 4
MAR 2 1 2025
§11-280.1-26
7/8/21; comp MAR2l?OZ5
(Auth:
HRS §§342L-3, 342L-32)
(Imp: HRS
§§342L-3, 342L-32)
§11-280.1-26
Performance standards and design
for UST systems--codes of practice.
(a)
The
following codes of practice may be used to comply with
section 11-280.1-20 (b) (1):
(1)
Underwriters Laboratories Standard 1316,
"Glass-Fiber-Reinforced Plastic Underground
Storage Tanks for Petroleum Products,
Alcohols, and Alcohol-Gasoline Mixtures"; or
(2)
Underwriter's Laboratories of Canada S615,
"Standard for Reinforced Plastic Underground
Tanks for Flammable and Combustible
Liquids".
(b)
The following codes of practice may be used
to comply with section 11-280.1-20(b) (2):
(1)
Steel Tank Institute "Specification STI-P3m
Specification and Manual for External
Corrosion Protection of Underground Steel
Storage Tanks";
(2)
Underwriters Laboratories Standard 1746,
"External Corrosion Protection Systems for
Steel Underground Storage Tanks";
(3}
Underwriters Laboratories of Canada S603,
"Standard for Steel Underground Tanks for
Flammable and Combustible Liquids", and
S603.1, "Standard for External Corrosion
Protection Systems for Steel Underground
Tanks for Flammable and Combustible
Liquids11
, and S631, "Standard for Isolating
Bushings for Steel Underground Tanks
Protected with External Corrosion Protection
Systems";
(4)
Steel Tank Institute Standard F841,
"Standard for Dual Wall Underground Steel
Storage Tanks"; or
{5)
NACE International Standard Practice SP
0285, "External Corrosion Control of
280.1-29
3 5 8 4
§11-280.1-26
Underground Storage Tank Systems by Cathodic
Protection", and Underwriters Laboratories
Standard 58, "Standard for Steel Underground
Tanks for Flammable and Combustible
Liquids".
(c)
The following codes of practice may be used
to comply with section 11-280.1-20(b) (3):
(1)
Underwriters Laboratories Standard 1746,
( 2)
( 3)
( 4 )
( d)
to comply
(1)
( 2)
( e)
to comply
( 1)
( 2)
(3)
"External Corrosion Protection Systems for
Steel Underground Storage Tanks";
Steel Tank Institute ACT-100ø Specification
F894, "Specification for External Corrosion
Protection of FRP Composite Steel
Underground Storage Tanks";
Steel Tank Institute ACT-100-Uù Specification
F961, "Specification for External Corrosion
Protection of Composite Steel Underground
Storage Tanks"; or
Steel Tank Institute Specification F922,
"Steel Tank Institute Specification for
Permatank11w .
The following codes of practice may be used
with section 11-280.1-20 (c) (1):
Underwriters Laboratories Standard 971,
"Nonmetallic Underground Piping for
Flammable Liquids"; or
Underwriters Laboratories of Canada Standard
S660, "Standard for Nonmetallic Underground
Piping for Flammable and Combustible
Liquids".
The following codes of practice may be used
with section 11-280.1-20 (c) (2):
American Petroleum Institute Recommended
Practice 1632, "Cathodic Protection of
Underground Petroleum Storage Tanks and
Piping Systems";
Underwriters Laboratories Subject 971A,
"Outline of Investigation for Metallic
Underground Fuel Pipe";
Steel Tank Institute Recommended Practice
R892, "Recommended Practice for Corrosion
Protection of Underground Piping Networks
280.1-30
3 5 8 I
§11-280.1-26
Associated with Liquid Storage and
Dispensing Systems";
(4)
NACE International Standard Practice SP
0169, "Control of External Corrosion on
Underground or Submerged Metallic Piping
Systems"; or
(5)
NACE International Standard Practice SP
0285, "External Corrosion Control of
Underground Storage Tank Systems by Cathodic
Protection".
(f)
Tank and piping system installation
practices and procedures described in the following
codes of practice may be used to comply with the
requirements of section 11-280.1-20(e):
(1)
American Petroleum Institute Publication
1615, "Installation of Underground Petroleum
Storage System";
(2)
Petroleum Equipment Institute Publication
RPlOO, "Recommended Practices for
Installation of Underground Liquid Storage
Systems"; or
(3)
National Fire Protection Association
Standard 30, "Flammable and Combustible
Liquids Code" and Standard 30A, "Code for
Motor Fuel Dispensing Facilities and Repair
Garages".
(g)
When designing, constructing, and installing
airport hydrant systems and UST systems with field
constructed tanks, owners and operators may use
military construction criteria, such as Unified
Facilities Criteria (UFC) 3-460-01, "Petroleum Fuel
FaciliVA_llz"t zolõff 7/15/18; comp 1/17/20; comp 7/8/21;
comp
Z3
)
(Auth:
HRS §§3421-3, 3421-32)
(Imp:
HRS §§3421-3, 3421-32)
§