HAR §19-37-9
HAR §19-37-9. Fire extinguishers
Length: 476 wordsOfficial source
Cite as Haw. Code R. § 19-37-9
These requirements
apply to all operation, maintenance, and use of aircraft
refueler
( 1 )
( 2)
( 3)
( 4)
units:
Each aircraft fuel servicing tank vehicle shall
have two listed extinguishers, each having a
rating of at least 208 mounted one on each side
of the vehicle.
Each aircraft servicing hydrant vehicle shall
have one extinguisher having a rating of at least
208 mounted.
Extinguishers must be readily accessible from the
ground.
The area paneling or tank shell adjacent
to or immediately behind the extinguisher(s) on
fueling vehicles shall be painted with a
contrasting color;
Only dry chemical and halon extinguishing agents
are permissible for use on fuel spills.
(5)
Service Stations shall have at least one fire
extinguisher with a minimum 20-B:C classification
and it shall be so located that no pump or
dispenser is more than seventy-five feet from one
such extinguisher;
(6)
When the open-hose discharge capacity of the
aircraft fueling system is not more than two
37-7
§19-37-13
hundred gallons per minute, at least two
extinguishers having a minimum 20-B:C
classification shall be provided.
(7)
When the open-hose discharge capacity of the
aircraft fueling system is more than two hundred
gallons per minute but not over three hundred
and fifty gallons per minute, at least one
wheeled extinguisher having a minimum 80-B:C
classification and having a minimum capacity of
one hundred and twenty-five pounds of agent shall
be provided.
(8)
When the open-hose discharge capacity of the
aircraft fueling system is more than three
hundred and fifty gallons per minute, at least
two wheeled extinguishers having a minimum 80-8:C
classification each and having a minimum capacity
of one hundred and twenty-five pounds of agent
each shall be provided.
(9)
Report use.
Use of any extinguisher equipment
under any circumstances shall be reported to the
Fire Chief immediately after use.
[Eff 2/26/93; am and comp JUL - 5 2025
(Auth:
HRS §261-12} (Imp:
HRS §261-12)
§19-37-10
Marking of aircraft fuel servicing
vehicles.
Each aircraft fuel servicing vehicle shall:
(1)
Have a sign permanently positioned on each side
and on the rear of every fuel carrying vehicle
identifying the product;
(2)
Have letters at least three inches high of a
color contrasting with the background and color
of the vehicle;
(3)
Show the word "FLAMMABLE" and the name of the
fuel carried, such as "JET FUEL" or "GASOLINE";
(4)
Have a placard 10 3/4" on each side and on the
rear of the vehicle in compliance with guidelines
on use of placarding in title 49 Code of Federal
Regulations Sections 172.500, 172.101, and
172.102;
37-8
§19-37-13
(5)
Have nEMERGENCY FUEL SHUTOFF" placarded in
letters at least two inches (fifty mm) high;
(6)
Show the method of operation by an arrow or by
the words "PUSH" or "PULL" as applicable.
(Eff 2/26/93; comp JUL -5 2025
) (Auth:
HRS
§261-12) (Imp:
HRS §261-12)