HAR §11-45-33
HAR §11-45-33. Shielding evaluation
Cite as Haw. Code R. § 11-45-33
(a) Before construction,
the construction plans of all new facilities, or modifications of
existing facilities, utilizing sources of radiation shall be
submitted to the department for review and approval. These plans
shall show, as a minimum, the following:
(1)
Normal location of the source of radiation;
(2)
General direction(s) of the useful beam for x-ray
devices;
(3)
Locations of any windows and doors;
(4)
If the source of radiation is an x-ray device, the
location of the operator's booth or position and the
location of the control assembly;
(5)
Structural composition, dimensions, and thickness of
all walls, doors, partitions, floor, and ceiling of
room(s);
(6)
Dimensions and thickness of lead (in inches,
millimeters, or nominal weight in pounds for a one
square foot section) specified for walls, doors,
partitions, floors, or ceiling of room(s);
(7)
Dimensions of the room(s);
(8)
Type of occupancy of all adjacent rooms and areas
inclusive of space above and below the room(s) with
sources of radiation; and
(9)
If there is an exterior wall, the distance to the
closest area(s) where it is likely that individuals
may be present.
(b)
The licensee or person intending to establish a
facility or operation with sources of radiation shall utilize the
services of a qualified medical physicist to determine the
shielding requirements of the new facility or modification of an
existing facility. A written shielding evaluation report by the
qualified medical physicist shall be submitted with the
architectural and electrical plans to the department as specified
in subsection (a). The evaluation report shall include, but not
limited to:
(1)
The anticipated workload or exposure from the source
§11-45-33
45-48
of radiation; and
(2)
All basic assumptions used in the development of the
shielding specifications.
(3)
All other relevant shielding specifications.
(c)
The shielding specifications on the construction plan
shall be equal or greater than the shielding specifications
identified on the qualified medical physicist's shielding
evaluation report.
(d)
The approval of radiation shielding by the department
shall not preclude the requirement of additional modifications
should a subsequent analysis of operating conditions indicate a
change in spatial relationship in the radiation facility or
conditions which may be contrary to the requirements in subchapter
4.
(e)
A shielding evaluation before construction is optional
for the following:
(1)
Dental facilities;
(2)
Podiatric facilities; or
(3)
Facilities determined by the department.
[Eff 11/12/99] (Auth: HRS §§321-10, 321-11, 321-71)
(Imp: HRS §§321-1, 321-11(21), 321-71)