HAR §11-62-34
HAR §11-62-34. (F) The distribution line shall be carefully placed on the bedding at a uniform slope and covered with at least two inches of gravel or stone
Length: 482 wordsOfficial source
Cite as Haw. Code R. § 11-62-34
(G) The ends of the distribution lines shall be capped or plugged.
(b) Deep absorption trenches. Deep absorption trenches may be considered where the depth of suitable soil is insufficient to permit the installation of a conventional trench system due to the presence of a limiting layer more than two feet in depth which overlies suitable soils of sufficient thickness. Requirements for location, design, slope, material, construction, and dosing system design contained in subsection (a) shall apply to deep absorption trenches except for depth of construction. In addition, the following design considerations shall apply:
(1) The site evaluation procedure shall include soil profile observations of at least three soil observation pits constructed to a minimum depth of three feet below the proposed trench bottom. Monitoring to establish depth to seasonal soil saturation or high groundwater may be considered;
(2) Deep absorption trenches shall be constructed at least one foot into the suitable soil; and
(3) The distribution piping in deep absorption trenches shall be installed with the invert of the piping at a depth of not more than thirty inches. Gravel or crushed stone shall be placed from the bottom of the trench excavation to a point two inches above the top of the distribution piping.
(c) Absorption beds.
(1) Location.
(A) Absorption beds shall be located in accordance with section 11-62-32.
(B) Absorption beds shall not be constructed in soils with a percolation rate slower than sixty minutes per inch or where rapid percolation may result
62-62
B176
§11-62-34
in contamination of water-bearing
formations or surface waters.
(C) Absorption beds shall be located on the
property to maximize the vertical
separation distance from the bottom of
the absorption bed to the seasonal high
groundwater level, bedrock, or other
Limiting layer, but under no
circumstance shall the vertical
separation be less than three feet.
The director may require a greater
vertical separation where water-bearing
formations are in danger of
contamination.
(D) Absorption beds shall not be
constructed in unstabilized fill.
(2) Design.
(A) The minimum area for any absorption bed
system shall be based upon a flow of
200 gallons per bedroom per day and in
accordance with Appendix D, Table III
dated July 1, 2014 and located at the
end of this chapter.
(B) The absorption area shall be computed
using the bottom area of the absorption
bed.
(C) Each soil absorption bed system shall
have a minimum of two distribution
lines.
(D) If more than one absorption bed is
designed, each absorption bed shall be
equal in area.
(E) The maximum length of any distribution
line shall be one hundred feet.
(F) Distribution lines within an absorption
bed shall be uniformly spaced no more
than six nor less than four feet apart.
(G) Distribution lines within an absorption
bed shall be placed no more than three
feet nor less than eighteen inches from
the sidewall of the bed.
62-63