HAR §11-95-9
HAR §11-95-9. Construction requirements
Cite as Haw. Code R. § 11-95-9
(a) The
facility shall be constructed and maintained in
accordance with state and county zoning, building, fire
safety, and sanitation laws, ordinances, and rules. New
construction and remodeling shall be guided by "Minimum
Requirements of Construction & Equipment for Hospital &
Medical Facilities" DHEW Publication No. (HRA) 79-14500
as it existed on December 31, 1984.
(b)
The facility shall be accessible to and
functional for physically handicapped persons.
(c)
There shall be adequate space to allow free
movement of occupants using wheelchairs, walkers, canes
and crutches to and from exits, post-operative recovery
areas, bathrooms, closets, dressing areas, and common
hall areas.
(d)
Provision shall be made for each patient to
have use of a lockable closet, dressing cubicle, or
dressing room.
(e)
A waiting room of appropriate size shall be
provided and toilet rooms, separate from patient
toilets, shall be easily accessible to those in the
waiting area.
(f)
Suitable dressing areas and toilet facilities
for staff use, separate from patient use, shall be
provided.
(g)
One or more examining rooms separate from
recovery and operating rooms shall be provided.
(h)
Grab bars shall be provided in patient and
waiting room toilets. Each bathroom shall provide at
least one washbasin and one commode.
(i)
Operating and recovery rooms shall be located
so as to prevent through traffic except in the case of
emergency. Entrance and exits to these rooms shall be
by means of interior doors except for emergency outdoor
exit doors which may be provided as needed.
(j)
There shall be adequate scrub-up facilities
and work areas for the preparation, sterilization, and
storage of instruments and supplies.
(k)
Each patient toilet and bathroom facility
shall have a suitable nurses' call system for signalling
the need for assistance.
(l)
Adequate supply of hot and cold potable
running water must be supplied at all times.
Temperature of hot water at plumbing fixtures used by
patients shall be automatically regulated and shall not
exceed 110˚F.
(m)
Bedpans and urinals shall be available for use
as well as suitable methods and equipment for cleaning
and sterilizing same.
(n)
In the event that a sexually mixed recovery
room is utilized, suitable screens or curtains shall be
provided to ensure privacy for each patient.
(o)
Patient beds, wherever located, shall be
surrounded by at least three feet of clear floor area.
(p)
All rooms in which patient care is carried out
shall be on or above grade level.
(q)
Floors and walls.
(1)
Floors shall be of slip resistant material,
flush at doorways.
(2)
Floors shall be of material which does not
retain odors.
(3)
Scatter rugs shall not be used.
(4)
Walls, floors, ceilings and decorative items
in rooms shall be made of material which
permit washing, cleaning, and painting.
(r)
Where appropriate, screening of doors and
windows shall be provided using screening having sixteen
meshes per inch.
(s)
Neither sliding doors nor folding doors shall
be used as room or building exit doors. All
double-acting doors shall be provided with vision
panels.
(t)
The minimum clear width of corridors shall be
forty-four inches, except when a general anesthetic is
used in the facility. In the latter case, corridors
which serve non-ambulatory patients shall be a minimum
of eight feet wide.
(u)
Suitable locked storage space shall be
available for storing of maintenance equipment and
supplies.
(v)
The water supply shall comply with chapter
340E, HRS.
(w)
Ventilation shall comply with chapter 11-39,
relating to air conditioning and ventilating.
(x)
Additions, alterations, and all repairs to
existing buildings.
(1)
Where the structure was in use for this type
of occupancy prior to the effective date of
this chapter, the director may waive or modify
any portion of these construction standards,
provided the exceptions do not create a hazard
to patients personnel or public. In no case
shall any fire safety standards, as determined
by the county fire marshal, be waived or
modified;
(2)
Drawings and specifications for all new
construction or additions, alterations, or
repairs to existing buildings subject to the
provisions of this chapter shall be submitted
to the licensing branch of the department for
review, and a certificate of need where
applicable, shall also be submitted.
(3)
Construction shall not commence prior to the
department's approval of construction
drawings. Specifications shall comply with
this chapter, the county fire marshal's rules,
and with county building codes and ordinances;
(4)
The department shall review each submittal and
advise the applicant, in writing, of its
findings, within a reasonable time, with
respect to approval, disapproval, or any
mandatory changes required;
(5)
Unless construction is commenced within one
year of the approval of final construction
drawings and specifications, the latter with
the previously approved application, shall be
resubmitted for review and reapproval;
(6)
Minor alterations which do not affect
structural integrity or fire safety and do not
change functional operation and do not
increase beds or services over that for which
the facility is licensed, may be submitted
either by freehand drawings or by the more
conventional drawings and specifications.
(y)
There shall be appropriately equipped utility
rooms, at least one clean and one soiled for each
operating suite. [Eff March 3, 1986] (Auth: HRS
§§321-9, 321-10) (Imp: HRS §§46-4, 62-34, 64-91, 65-71,
66-71, 70-71, 132-3, 321-10, 340E-1 to 340E-9)