HAR §12-221.1-4

HAR §12-221.1-4. Boiler blowoff equipment

Last amended: 2019Length: 96 wordsOfficial source

Cite as Haw. Code R. § 12-221.1-4

(a) The blowdown from a boiler or boilers that enters a sanitary sewer system or blowdown that is considered a hazard to life or property shall pass through some form of blowoff equipment that will: (1) Prevent water exceeding 150 degrees Fahrenheit from leaving the blowoff equipment; and 221.1-2 (2) Prevent the pressure leaving the blowdown of any blowoff equipment to exceed five (5) psig. (b) Blowoff equipment shall conform to the provisions set forth in NB-27 "A Guide to Blowoff Vessels". [Eff and comp DEC 2 1 2019 ] (Auth: HRS §397-4) (Imp: HRS §397-4)