HAR §12-223.1-7. water column to a boiler for introduction of feedwater into a boiler
Length: 1,898 wordsOfficial source
Cite as Haw. Code R. § 12-223.1-7
If the water column, gage glass, low-water fuel cutoff, or other water level control device is connected to the boiler by pipe and fittings, no shutoff valves of any type shall be placed in such pipe and a cross or equivalent fitting to which a drain valve and piping may be attached shall be placed in the water piping connection at every right angle turn to facilitate cleaning and inspection. The water column drain pipe and valve shall be not less than 3/4-inch diameter; and
(B) The steam connections to the water column of a horizontal firetube wrought boiler shall be taken from the top of the shell or the upper part of the head, and the water connection shall be taken from a point not above the center line of the shell. For a cast-iron boiler, the steam connection to the water column shall be taken from the top of an end section or the top of the steam header, and the water connection shall be made on an end section not less than six (6) inches below the bottom connection to the water-gage glass;
(4) Pressure control. The following shall apply to pressure control:
(A) Each automatically fired steam boiler shall be protected from overpressure by two pressure-operated controls. Each individual steam boiler or each system of commonly connected steam heating boilers shall have a control that will cut off the fuel supply when the steam pressure reaches an operating limit, which shall be less than the maximum allowable pressure;
(B) Each individual automatically fired steam boiler shall have a safety limit control, with a manual reset that will cut off the
223.1-13
§12-223.1-7
fuel supply to prevent steam pressure
from exceeding the fifteen (15) psig
maximum allowable working pressure of the
boiler. Each control shall be constructed
to prevent a pressure setting above
fifteen (15) psig;
(C) Shutoff valves of any type shall not be
placed in the steam pressure connection
between the boiler and the controls
described in subparagraphs (A) and (B).
These controls shall be protected with a
siphon or equivalent means of maintaining
a water seal that will prevent steam from
entering the control. The connections to
the boiler shall not be less than NPS 1/4
for lengths up to five (5) feet, but
where steel or wrought iron pipe or
tubing is used, they shall not be less
than NPS 1/2 for lengths up to five (5)
feet, and not less than NPS 1 for lengths
over five (5) feet. The minimum size of
an external siphon shall be NPS 1/4 or
3/8 inch outside diameter nonferrous
tubing. For manifold connections, the
minimum size shall be as specified in the
original code of construction; and
(D) Pressure controls should have separate
connections, however, manifolding is
permitted. When multiple pressure
controls are connected to the boiler with
a common manifold, the connection at the
boiler up to and including the entire
manifold, for pipe of nonferrous
material, shall not be less than NPS 1/2
for lengths up to five (5) feet, and not
less than NPS 3/4 for lengths over five
(5) feet. For manifolds using ferrous
material, the connection at the boiler up
to and including the entire manifold
shall not be less than NPS 3/4 for
lengths up to five (5) feet, and not less
than NPS 1-1/4 for lengths over five (5)
feet. Individual controls are to be piped
223.1-14
3559
§12-223.1-7
from the manifold according to the provisions of subparagraph (C);
(5) Automatic low-water fuel cutoff and water feeding devices. The following shall apply to automatic low-water fuel cutoff and water feeding devices:
(A) Each automatically fired steam boiler shall have an automatic low-water fuel cutoff. The low-water fuel cutoffs must be located to automatically cut off the fuel supply when the surface of the water falls to a level not lower than the lowest visible part of the water-gage glass. If a water feeding device is installed, it shall be so constructed that the water inlet valve cannot feed water into the boiler through the float chamber and so located as to supply requisite feedwater;
(B) Such a fuel cutoff or water feeding device may be attached directly to a boiler. A fuel cutoff or water feeding device may also be installed in the tapped openings available for attaching a water glass directly to a boiler, provided the connections are made to the boiler with nonferrous tees or Y fittings not less than NPS 1/2 between the boiler and water glass so that the water glass is attached directly and as close as possible to the boiler; the run of the tee or Y-fitting shall take the water glass fittings, and the side outlet or branch of the tee or Y-fittings shall take the fuel cutoff or water feeding device. The ends of all nipples shall be reamed to full-size diameter;
(C) In addition to the requirements in subparagraphs (A) and (B), a secondary low-water fuel cutoff with manual reset shall be provided on each automatically fired steam boiler; and
223.1-15
3559
§12-223.1-7
(D) Fuel cutoffs and water feeding devices embodying a separate chamber shall have a vertical drain pipe and a blowoff valve not less than NPS 3/4, located at the lowest point in the water equalizing pipe connections so that the chamber and the equalizing pipe can be flushed and the device tested.
(b) Hot-water heating or hot-water supply boilers. The following shall apply to hot-water heating or hot-water supply boilers:
(1) Pressure or altitude gages:
(A) Each hot-water heating or hot-water supply boiler shall have a pressure or altitude gage connected to it or to its flow connection in such a manner that it cannot be shut off from the boiler except by a cock with tee or lever handle, placed on the pipe near the gage. The handle of the cock shall be parallel to the pipe in which it is located when the cock is open;
(B) The scale on the dial of the pressure or altitude gage shall be graduated approximately to not less than one and a half (1-1/2) nor more than three and a half (3-1/2) times the pressure at which the safety relief valve is set; and
(C) Piping or tubing for pressure or altitude gage connections shall be of nonferrous metal when smaller than NPS 1;
(2) Thermometers: each hot-water heating or hot-water supply boiler shall have a thermometer so located and connected that it shall be easily readable. The thermometer shall be so located that it shall always indicate the temperature of the water in the boiler at or near the outlet;
(3) Temperature controls. Each automatically fired hot-water heating or hot-water supply boiler shall be protected from over-temperature by two temperature-operated controls. The following shall apply to automatically fired
223.1-16
3559
§12-223.1-7
hot-water heating and hot-water supply boilers:
(A) Each individual hot-water heating or hot-water supply boiler or each system of commonly connected heating boilers shall have at least one control that will cut off the fuel supply when the water temperature reaches an operating limit, which shall be less than the maximum allowable temperature; and
(B) Each individual automatically fired hot-water heating or hot-water supply boiler shall have a safety limit control with manual reset that will cut off the fuel supply to prevent the water temperature from exceeding the maximum allowable temperature at the boiler outlet;
(C) Each operating and safety limit control shall have its own sensing element and operating switch; and
(D) Alternately, integrated controls with multiple sensors may be used to meet the requirements of subparagraphs (A) and (B);
(4) Low-water fuel cutoff. The following shall apply to automatically fired hot-water heating boilers:
(A) Each automatically fired hot-water heating boiler shall have an automatic low-water fuel cutoff with manual reset. The low-water fuel cutoff shall be designed for hot-water service, and it shall be so located as to automatically cut off the fuel supply when the surface of the water falls to the level established in subparagraph (B);
(B) As there is no normal waterline to be maintained in a hot-water boiler, any location of the low-water fuel cutoff above the lowest safe permissible water level established by the boiler manufacturer is satisfactory;
223.1-17
3559
§12-223.1-7
(C) In lieu of the requirements for low-water fuel cutoffs in subparagraph (A), heating boilers requiring forced circulation to prevent overheating of the tubes, coils, or vessel, shall have an accepted flow-sensing or temperature-sensing device to prevent burner operation at a flow rate inadequate to protect the boiler unit against overheating at all allowable firing rates. This safety control(s) shall shut down the burner and prevent restarting until an adequate flow is restored and shall be independent of all other controls; and
(D) A means shall be provided for testing the operation of the external low-water fuel cutoff without resorting to draining the entire system. Such means shall not render the device inoperable except as follows: if the means temporarily isolates the device from the boiler during this testing, it shall automatically return to its normal position. The connection may be so arranged that the device cannot be shut off from the boiler except by a cock placed at the device and provided with a tee or lever-handle arranged to be parallel to the pipe in which it is located when the cock is open;
(c) Potable water heaters. The following shall apply to potable water heaters:
(1) Temperature controls. The following shall apply to the temperature controls of potable water heaters:
(A) Each individual automatically fired water heater, in addition to the operating control used for normal water heater operation, shall have a separate high limit temperature actuated combustion control that will automatically cut off the fuel supply. The temperature range of the high limit temperature actuated
223.1-18
3559
§12-223.1-7
control shall not allow a setting over 210 degrees Fahrenheit;
(B) Gas-fired water heaters: the high limit temperature control when actuated shall shut off the fuel supply with a shutoff means other than the operating control valve. Separate valves may have a common body;
(C) Electrically heated water heaters: the high limit temperature control when actuated shall cut off all power to the operating controls;
(D) Oil-fired water heaters: the high limit temperature control when actuated shall cut off all current flow to the burner mechanism; and
(E) Indirect water heating systems: the high limit temperature control when activated shall cut off the source of heat;
(2) Pressure or altitude gages. The following shall apply to pressure or altitude gages:
(A) Each potable water heater shall have a pressure or altitude gage connected to it or to its flow connection in such a manner that it cannot be shut off from the boiler except by a cock with tee or lever handle placed on the pipe near the gage. The handle of the cock shall be parallel to the pipe in which it is located when the cock is open;
(B) The scale on the dial of the pressure or altitude gage shall be graduated approximately to not less than one and a half (1-1/2) nor more than three (3) times the maximum allowable working pressure; and
(C) Piping or tubing for pressure or altitude gage connections shall be of nonferrous metal when smaller than 1-inch pipe size;
(3) Thermometers: each installed water heater shall have a thermometer so located and
223.1-19
559