HAR §12-224.1-5
HAR §12-224.1-5. vessel
Length: 1,219 wordsOfficial source
Cite as Haw. Code R. § 12-224.1-5
Pressure vessels with multiple chambers with different maximum allowable working pressures shall have a pressure relief device to protect each chamber under the most severe coincident conditions;
(3) Location. The following shall apply to location of devices:
(A) The pressure relief device shall be installed directly on the pressure vessel, unless the source of pressure is external to the vessel and is under such positive control that the pressure cannot exceed the maximum overpressure permitted by the original code of construction and the pressure relief device cannot be isolated from the vessel, except as permitted by NBIC Part 1, 4.5.6(e)(2);
(B) Pressure relief devices intended for use in compressible fluid service shall be connected to the vessel in the vapor space above any contained liquid or in the piping system connected to the vapor space; and
(C) Pressure relief devices intended for use in liquid service shall be connected below the normal liquid line. The liquid level during upset conditions shall be considered;
(4) Capacity. The following shall apply to the capacity of pressure relief devices:
(A) The pressure relief device(s) shall have sufficient capacity to ensure that the pressure vessel is not exposed to pressure greater than that specified in the original code of construction;
(B) Vessels connected by a system of piping not containing valves that can isolate any pressure vessel shall be considered as one unit when determining capacity requirements;
(C) Heat exchangers and similar vessels shall be protected with a pressure relief device of sufficient capacity to avoid
224.1-7
3559
§12-224.1-5
overpressure in case of internal failure;
and
(D) The owner shall make information
regarding the basis of pressure relief
device selection, including required
capacity, available to the jurisdiction;
(5) Set pressure. The following shall apply to the
set pressure of pressure relief devices:
(A) When a single pressure relief device is
used, the set pressure marked on the
device shall not exceed the maximum
allowable working pressure; and
(B) When more than one pressure relief device
is provided to obtain the required
capacity, only one pressure relief device
set pressure needs to be at the maximum
allowable working pressure. The set
pressures of the additional pressure
relief devices shall be such that the
pressure cannot exceed the overpressure
permitted by the code of construction;
and
(6) Installation and discharge piping
requirements. The following shall apply to the
installation and discharge piping of pressure
relief devices:
(A) The opening through all pipe and fittings
between a pressure vessel and its
pressure relief device shall have at
least the area of the pressure relief
device inlet. The characteristics of this
upstream system shall be such that the
pressure drop will not reduce the
relieving capacity below that required or
adversely affect the proper operation of
the pressure relief device. When a
discharge pipe is used, the size shall be
such that any pressure that may exist or
develop will not reduce the relieving
capacity below that required or adversely
affect the proper operation of the
pressure relief device. It shall be as
short and straight as possible and
224.1-8
3559
§12-224.1-5
arranged to avoid undue stress on the pressure relief device;
(B) A non-reclosing device installed between a pressure vessel and a pressure relief valve shall meet the requirements of subparagraph (A);
(C) The opening in the pressure vessel wall shall be designed to provide unobstructed flow between the vessel and its pressure relief device;
(D) When two or more required pressure relief devices are placed on one connection, the inlet cross-sectional area of this connection shall be sized either to avoid restricting flow to the pressure relief devices or made at least equal to the combined inlet areas of the pressure relief devices connected to it. The flow characteristics of the upstream system shall satisfy the requirements of NBIC Part 1, 4.5.6(e); and
(E) There shall be no intervening stop valves between the vessel and its pressure relief device(s), or between the pressure relief device(s) and the point of discharge, except under the following conditions:
(i) When these stop valves are so constructed or positively controlled that the closing of the maximum number of block valves at one time will not reduce the pressure relieving capacity below the required relieving capacity;
(ii) Upon specific acceptance of the jurisdiction, when necessary for the continuous operation of processing equipment of such a complex nature that shutdown of any part is not feasible, a full area stop valve between a pressure vessel and its pressure relief device shall be provided for inspection and repair purposes only. This stop valve shall
224.1-9
3559
§12-224.1-5
be arranged so that it can be locked or sealed open, and it shall not be closed except by an authorized person who shall remain stationed there during that period of operation while the valve remains closed. The valve shall be locked or sealed in the open position before the authorized person leaves the station;
(iii) A full area stop valve shall also be placed on the discharge side of a pressure relief device when its discharge is connected to a common header for pressure relief devices to prevent discharges from these other devices from flowing back to the first device during inspection and repair. This stop valve shall be arranged so that it can be locked or sealed open, and it shall not be closed except by an authorized person who shall remain stationed there during that period of operation while the valve remains closed. The valve shall be locked and sealed in the open position before the authorized person leaves the station. This valve shall only be used when a stop valve on the inlet side of the pressure relief device is first closed;
(iv) A pressure vessel in a system where the pressure originates from an outside source shall have a stop valve between the vessel and the pressure relief device, and this valve need not be sealed open, provided it also closes off that vessel from the source of the pressure;
(v) All pressure relief devices shall
224.1-10
3559
§12-224.1-5
releive to a safe point of
discharge;
(vi) Discharge lines from pressure relief
devices shall be designed to
facilitate drainage or be fitted
with drains to prevent liquid from
collecting in the discharge side of
a pressure relief device. The size
of discharge lines shall be such
that any pressure that may exist or
develop will not reduce the
relieving capacity of the pressure
relief device or adversely affect
the operation of the pressure relief
device. It shall be as short and
straight as possible and arranged to
avoid undue stress on the pressure
relief device;
(vii) Pressure vessel pressure relief
devices and discharge piping shall
be safely supported. The reaction
forces due to discharge of pressure
relief devices shall be considered
in the design of the inlet and
discharge piping. Design of
supports, foundations, and settings
shall consider vibration (including
seismic when necessary), movement
(including thermal movement), and
loadings (including reaction forces
during device operation) in
accordance with jurisdictional
requirements, manufacturer's
recommendations, and/or other
industry standards, as applicable;
and
(viii) Pressure relief devices shall be
installed so they are readily
accessible for inspection, repair,
or replacement.
(e) Supports. Pressure vessels and associated
piping shall be safely supported. The potential for
future pressure tests of the vessel after installation
224.1-11
3559