HAR §12-250-10
HAR §12-250-10. Electrical safety requirements
Cite as Haw. Code R. § 12-250-10
(a) All electrical wiring,
equipment, and apparatus used for amusement rides or for lighting shall be
properly and legally installed, operated, and maintained, as required by NFPA
70 and local ordinances.
(b)
No employee shall be suffered or permitted to work in such
proximity to any part of electrical power circuits that the employee may
contact the same in the course of the work unless protected against shock by
de-energizing the circuit, grounding it, or guarding it by effective
insulation. If protection is supplied by de-energizing the circuit, the
switch controlling the circuit shall be locked out to prevent inadvertent
closing.
(c)
The outlets of electric power lines carrying more than 120 volts
shall be clearly marked to show their voltage.
(d)
All electric transformer sub-stations shall be properly enclosed
and proper warning signs shall be posted.
(e)
Electrical apparatus and wiring located outdoors shall be of such
quality and so constructed or protected that exposure to weather will not
interfere with its normal operation or endanger life or property.
(f)
Elevated power lines crossing access or other roads within the
grounds of the carnival, circus, fair, amusement parks, or other areas where
the amusement rides are located shall be so suspended as to provide minimum
vertical clearance of 12 feet (3.6 m) from the road surface and minimum
horizontal clearance of 3 feet (90 cm) from each side of the normal passage
Page 5
space of vehicles.
(g)
Wiring laid on or under surfaces traversed by vehicular or
pedestrian traffic shall be adequately protected against wear and abrasion.
Buried cables shall be Type UF as required by Article 339 of NFPA 70.
(h)
Temporary electric wiring if suspended shall be so supported that
its protective insulation will not be damaged.
(i)
All electrical installations shall be properly grounded. All
electrical cords shall be of the heavy duty type and shall contain an
identifying grounding conductor in addition to the current-carrying
conductors. The size of grounding conductor shall comply with Table 250-94 of
NFPA 70.
(j)
Bare wires and other uninsulated current-carrying parts shall be
guarded against accidental contact by means of proper location or by a fence
or other barrier.
(k)
Conductors shall be provided with over-current protective devices
according to load and current-carrying capacity. No such device shall be
installed on neutral or grounding conductors.
(l)
Where electrical power is supplied for an amusement ride by a
privately operated generating system, the generator and all equipment shall be
properly grounded if the system incorporates a ground.
(m)
All receptacles and attachment caps shall be of the grounding
type.
(n)
Each electrically powered amusement ride shall be effectively
grounded. The grounding shall be made effective as to all non-current-
carrying metal parts which may become energized and which are exposed to
contact by any person.
(o)
Each electrically operated amusement ride not designed to be
controlled directly by the passenger shall be provided with a disconnect power
switch placed within easy reach of the operator. [Eff. 12/6/82; am and ren
§12-250-10 and comp 12/6/90; am 7/6/98] (Auth: HRS §397-4) (Imp: HRS §397-4)