HAR §12-45.4-35
HAR §12-45.4-35. Storage of combustible materials
Length: 132 wordsOfficial source
Cite as Haw. Code R. § 12-45.4-35
Section
10.18.1.1 is added to read as follows: 10.18.1.1 Signage posting. In
storage and mercantile occupancies, a sign shall be posted on the
automatic sprinkler riser stating the maximum allowable storage height
for the design of the sprinkler system as approved by the AHJ.
[Eff ] (Auth: HRS §132-3) (Imp: HRS §132-3)
This was in previous state fire codes & adds an additional
requirement. It addresses the allowable storage height in these
occupancies based on the original design of the sprinklers system.
Businesses lease spaces in warehouses with high ceilings and
bring in high-piled storage racks, which the original sprinkler
system was not designed to control. This amendment assists the
fire inspector with identifying these cases. Lloyd relocated this
amendment into the general category instead of being in the
ceiling clearance section.)