HAR §12-45.4-42. Fire protection systems hose connection

Length: 126 wordsOfficial source

Cite as Haw. Code R. § 12-45.4-42

Section 13.1. 5.2 is added to read as follows: 13.1.5.2 Fire department hose connections serving standpipe and sprinkler systems shall be located within twenty feet of a fire apparatus access road, not less than eighteen inches and not more than four feet above grade, or as approved by the AHJ. Appropriate identification signs shall be provided as required by the AHJ. [Eff ] (Auth: HRS §132-3) (Imp: HRS §132-3) (This has been in previous state fire codes. It requires connections to be in readily accessible locations to roadways for fire department use. It incorporated two amendments, one for standpipes and one for sprinklers into one amendment for both types of connections. The heading title was changed to correspond with the chapter title in the fire code.