HAR §12-45.4-74
HAR §12-45.4-74. Other fire protection systems compliance
Length: 652 wordsOfficial source
Cite as Haw. Code R. § 12-45.4-74
Section 13.8 is amended to read as follows: Section 13.8. Other Fire
Protection Systems. Where other fire protection systems are required to
be installed by the provisions of this code, or are installed with the
approval of the AHJ as an alternative or equivalency, the design and
installation of the system shall comply with the appropriate standards
listed in Table 13.8. The systems shall be inspected, tested, and
maintained in accordance with the appropriate NFPA standard.
(Appropriate NFPA standards describe maintenance requirements.
The reference in the code to Section 10.4 is a reference to
Building Evacuation which is incorrect.)
§12-45.4-75 Other fire protection systems inspection,
testing, and maintenance label. Section 13.8 is amended to add as
follows: Section 13.8.1 Inspection, Testing, and Maintenance Label.
Other fire protection systems satisfactorily passing an inspection, testing,
and maintenance test shall have an approved label affixed to the manual
activation device or, if not present, actuator valve to the extinguishing
agent. The label shall, as a minimum, entail the following:
(1)
Removal of the previous label;
(2)
Indicate the type of system, month and year the system was
tested;
(3)
Certificate of fitness holder’s name and number;
(4)
Certificate of fitness holder’s company name, address and
contact information;
(5)
Be yellow, at least two and one-fourth of an inch in width,
and three and one-fourth of an inch in length;
(6)
Be constructed of a durable material approved by the AHJ;
(7)
Be clearly visible without obstructing the visibility or operation
of the system; and
(8)
Be punched with no more than one year and one month.
13.8.2 Hydrostatic Testing. Every twelve years from the date of
manufacture, stored pressure extinguishing agent cylinders shall be
hydrostatically tested.
13.8.3 Hydrostatic Testing Label. Stored pressure extinguishing
agent cylinders satisfactorily passing a twelve-year hydrostatic test shall,
as a minimum, have a label attached to the cylinder as follows:
(1)
Removal of the previous label.
(2)
Indicate the type of system, and month and year the system
was tested.
(3)
Certificate of fitness holder’s name and number.
(4)
Certificate of fitness holder’s company name, address, and
contact information.
(5)
Be yellow, at least two and one-fourth of an inch in width,
and three and one-fourth of an inch in length.
(6)
Be constructed of a durable material approved by the AHJ.
(7)
Be clearly visible without obstructing the visibility or operation
of the system.
(8)
Be punched with no more than one year and one month.
13.8.4 The fire department shall be verbally notified immediately
of any systems determined to be out of service. Systems that cannot be
utilized for firefighting operations shall have an inoperable system sign
affixed to the manual activation device. The sign shall remain in place
until all repairs have been made and a satisfactory system test is
completed.
13.8.5 Inspection, testing, and maintenance report. An inspection,
testing, and maintenance report entitled “Foam Water Sprinkler System”,
“Other Fire Protection Systems” available on the State Fire Council’s
website and at each county fire department’s fire prevention bureau, or a
similar report approved by the AHJ shall be provided to the property
owner or agent within fourteen days after the test.
(This revision standardizes the ITM report form & where it may be
found).
13.8.6 Inspection Report. An electronic copy of the unsatisfactory
test report shall be submitted to the AHJ within five working days. The
AHJ shall determine if the submittal of a satisfactory test report will be
required.
13.8.7 Table 13.2.3.4.3A entitled “Fire Protection Systems
Reference Dates” may be used as a reference for applicable codes and
standards in effect when the building was permitted.
[Eff ] (Auth: RCH §4-105; ROH §1-9.1; HRS §132-2)
(Imp: HRS §132)
(Table 13.8 lists the various NFPA standards for the different
types of systems. Exhibits provide additional system information.
It also adds additional information to the tag or label and
expedites the notification to the AHJ of a failed system.