HAR §12-45.5-69
HAR §12-45.5-69. Existing day-care and health care occupancies
Length: 770 wordsOfficial source
Cite as Haw. Code R. § 12-45.5-69
Section 13.7.2.6 & 13.7.2.8 is deleted in its entirety.
[Eff ] (Auth: HRS §132-3) (Imp: HRS §132-3)
This recognizes that this code does not retroactively apply to
existing day-care & health care occupancies that were
constructed to requirements in the building code of that time.)
§12-45.4-70 Fire alarm systems inspection, testing, and
maintenance notification. Section 13.7.3.2.4 is amended by adding
section 13.7.3.2.4.1.1 to read as follows: 13.7.3.2.4.1.1 The county fire
department shall be given a seventy-two hour notification prior to a
scheduled inspection, testing, maintenance or retesting of any fire alarm
systems within their respective jurisdiction. [Eff ]
(Auth: HRS §132-3) (Imp: HRS §132-3)
§12-45.4-71 Fire alarm systems inspection, testing, and
maintenance labels. Section 13.7.3.2.4 (this was misnumbered) is
amended by adding sections 13.7.3.2.4.4.1, 13.7.3.2.4.4.2,
13.7.3.2.4.4.3, and 13.7.3.2.4.4.4 to read as follows: 13.7.3.2.4.4.1
Labels. Fire alarm systems passing an annual inspection, testing, and
maintenance test shall have an approved label affixed to the annunciator
panel or, if not present, the fire alarm system control panel in accordance
with section 13.7.3.2. Information on the label, at a minimum shall,
entail the following:
(1)
Removal of the previous label;
(2)
Indicate the month and year the satisfactory test was
performed;
(3)
Certificate of fitness holder’s name and number;
(4)
Certificate of fitness holder’s company name, address, and
contact information;
(5)
Be yellow, at least two and one-fourth of an inch in width,
and three and one-fourth of an inch in length;
(6)
Be clearly visible without obstructing the visibility or operation
of the annunciator panel or, if not present, fire alarm system
control panel; and
(7)
The label shall be clearly visible and punched with no more
than one year and one month.
13.7.3.2.4.4.2 Fire alarm systems failing an annual inspection,
test, and maintenance test shall leave the expired inspection tag or label
in place on the annunciator panel or, if not present, the fire alarm system
control panel until the system is repaired.
13.7.3.2.4.4.3 The AHJ and the building owner shall be verbally
notified immediately when a fire alarm system becomes inoperable.
Alternative notification and response plans shall be implemented after
approved by the AHJ until the fire alarm system is fully operational.
13.7.3.2.4.4.4 An inspection, testing, and maintenance report
entitled “System Record of Inspection and Testing”, “Notification
Appliance Supplementary Record of Inspection and Testing”, “Initiating
Device Supplementary Record of Inspection and Testing”, “Mass
Notification System Supplementary Record of Inspection and Testing”,
“Emergency Communications Systems Supplementary Record of
Inspection and Testing”, “Interface Component Supplementary Record of
Inspection and Testing”, available on the State Fire Council’s website and
at each county fire department’s fire prevention bureau, or a similar
report approved by the AHJ shall be provided to the property owner or
agent within fourteen days after a satisfactory test.
[Eff ] (Auth: HRS §132-16) (Imp: HRS §132-16; SLH
2014, Act 165)
(This revision standardizes the ITM report form & where it may be
found. This adds additional information to the tag or label and
expedites the notification to the AHJ of an inoperable fire alarm
system. Exhibit B became Annex G)
§12-45.4-72 Fire alarm systems inspection, testing, and
maintenance tag. Section 13.7.3.2.4.7 is amended by adding as
follows: Section 13.7.3.2.4.7 Tag. A tag shall be placed on the fire alarm
panel when tested in accordance with NFPA 72. Information on the tag
shall include the date of testing, testing company and contact
information, technician performing the test and certificate of fitness
number, and that the test was satisfactory. [Eff ]
(Auth: HRS §132-3) (Imp: HRS §132-3)
(This was a consolidated county amendment from the NFPA Fire
Code 2006 edition into the 2012 edition. Sections changed from
2012 edition to 2015 & 2018 editions. This moved from
13.7.3.2.5 to 13.7.3.2.4.7. The reference in the amendment to
13.7.3.2 is incorrect. Should be NFPA 72 Chapter 14.)
§12-45.4-73 Fire alarm systems manually activated alarm-
initiating devices. Section 13.7.3.3.8.4 is amended to add a new
sentence at the end to read as follows: The location of manual fire alarm
boxes may be modified by the AHJ. [Eff ] (Auth: HRS
§132-3) (Imp: HRS §132-3)
(Section 13.7.3.3.6 in the 2012 edition is now 13.7.3.3.8.4 in the
2015 & 2018 editions. This amendment allows alternate locations
for fire alarm pull stations by the AHJ. An example is the
agreement between the State Department of Education and the
State Fire Council to allow pull stations to be placed inside of
classrooms with identification signs outside of those classrooms.
The justification was to reduce vandalism and false activations
with the rooms being accessible during school hours. This
amendment allows alternate locations for fire alarm pull stations
by the AHJ.