HAR §15-319-24
HAR §15-319-24. Backflow Preventer and Valves
Cite as Haw. Code R. § 15-319-24
(a)
Prohibition of certain connections and installations.
To provide proper sanitary protection to the
corporation's water supply, and to comply with the
applicable statutes, rules and regulations of the
United States Environmental Protection Agency and of
the state department of health, as presently adopted
and from time to time amended, no cross-connections
with other water supplies, or other physical
connections shall exist, or be installed, located,
maintained or operated, which could permit backflow of
contaminated water from the consumer's premises into
the corporation's water supply system, except as
provided below:
(1)
Cross-connections with other water supplies.
Existing water supplies which are in active
use and cross-connected to the corporation's
system will be allowed only under the
following conditions:
(A)
Where such water supplies are regularly
analyzed by the corporation, or other
agencies satisfactory to the
corporation, meet the requirements of
the State's Safe Drinking Water
Regulations and have no cross
connections which could permit
backflow of contaminated water into
those water supplies; and
(B)
Where such water supplies do not meet
the requirements of paragraph (1)
above, are not normally under pressure,
and are maintained solely for
firefighting purposes, and, where
adequate protection against backflow
to the corporation's water system is
provided by mechanical means, or other
methods or devices, satisfactory to
the corporation.
319-15
§15-319-24
(2)
Other physical connections. Other physical
connections may be permitted if, in the
judgment of the corporation, adequate
protection can be provided to the water
supply of the corporation against backflow
by the installation of mechanical or other
methods or devices, approved by the
corporation, and installed, maintained, and
operated by the consumer in a manner
satisfactory to the corporation at all
times; provided, however, that the
corporation may require the consumer to
eliminate or rearrange designated plumbing
or piping connections or fixtures, or to
install a backflow device at the meter or
other location, subject to the approval of
the corporation whenever
(1) the consumer is engaged in the handling of
dangerous or corrosive liquids or industrial or
process waters, highly contaminated water or
sewage, or is engaged in the medical or dental
treatment of persons who might have diseases
transmittable by water; or
(2) in the judgment of the corporation there
exists a danger of backflow into the
corporation's mains because of the possibility
of unauthorized connections being created
through noncompliance or inadvertence by reason
of the complexity of the system or systems; or,
because of failure by the consumer to provide
adequately qualified personnel and supervision
for maintenance and extension of the consumer's
piping system or systems; or, for any other
reason or cause deemed sufficient in the
corporation's discretion.
(b)
Separate pressure system. The corporation will
require the installation of mechanical or other
methods or devices, on the consumer's side of
the meter to prevent backflow whenever the
consumer maintains a separate pressure system or
a separate storage facility; or, in any way
increases the pressures of the water within the
319-16
§15-319-24
consumer's premises above the pressure furnished by
the corporation; or, has such equipment or
arrangement of piping, storage or industrial methods
or processes as might under certain conditions raise
the pressure of the water within the consumer's
premises above the pressure of the water in the mains
of the corporation. Plans for all such installations
must be approved by the corporation.
(c)
Location of protective devices. Any device
installed for the prevention of backflow as may
be required under this chapter shall unless the
corporation approves otherwise in writing, be
located above ground, and in such location as to
be safe from flooding or submergence in water or
other liquids, properly protected from external
damage, freely accessible, and with adequate
working room for testing and repairing.
All such devices shall be tested at least
once annually, and as often as required by the
corporation in those instances where successive tests
indicate repeated failure. Repairs, replacement of
parts, etc., shall be made whenever deemed necessary
by the corporation at the expense of the consumer.
Completing annual tests shall be the responsibility of
the consumer, and shall be performed only by the
consumer or such other qualified person or persons in
accordance with all applicable health and safety laws,
including section 11-21, Hawaii Revised Statutes, as
may be acceptable to the corporation. Records of all
tests shall be made on forms prescribed by the
corporation, and a copy of each such record shall be
promptly furnished to the corporation. If the consumer
fails to complete the proper tests and submission of
records, the corporation may, in its sole discretion,
complete the tests, needed repairs, and replacements,
and charge the costs thereof to the consumer.
(d)
Conformance with laws and ordinances. The
several conditions relative to installation
and maintenance of cross-connections and other
physical connections referred to in this
section shall be subject to the changing
requirements of state and federal health and
319-17
§15-319-24
environmental statutes, rules, regulations, or
other authority, and any applicable county building
code.
(e)
Discontinuance of water service for
noncompliance. Failure on the part of the
consumer to comply with the corporation's
requirements relative to cross-connections and
backflow prevention will be sufficient reason for
discontinuing water service until such time as
the corporation is satisfied the requirements
have been met.
(f)
If the consumer intends to use the corporation's
water system for agricultural use, the
corporation shall require the installation of
mechanical, or other methods or devices that have
been approved by the board of water supply of the
applicable county, on the consumer's side of the
meter to prevent backflow at the expense of the
consumer. Plans for such installations shall be
approved by the corporation.
As a protection to the consumer's plumbing
system, a suitable pressure relief valve must be
installed and maintained by the consumer at its
expense when backflow devices are installed on
the consumer's side of the meter.
(1) Upon request of the corporation, the consumer
shall present an affidavit certifying that there are
no connections with other water supply systems on the
consumer's premises; and
(2) The consumer's failure to comply with the
corporation's requirements for backflow prevention will be
sufficient reason for discontinuing water service until
such time as the requirements have been met.
[Eff OCT 2 3 2022
] (Auth: HRS §201H-4)
(Imp: HRS §201H-9)