32 Ill. Adm. Code 346.130
Specific License for Irradiators
Section 346.130 Specific License for Irradiators
The Agency will approve an
application for a specific license to operate an irradiator if the applicant
meets the requirements contained in this Section.
a) The
applicant shall satisfy the general requirements specified in 32 Ill.
Adm. Code 330.250 and the requirements contained in this Part.
b) The
application shall describe the training provided to irradiator operators including:
1) Classroom
training;
2) On-the-job
or simulator training;
3) Safety
reviews;
4) Means
employed by the applicant to test each operator's understanding of the Agency's
regulations and licensing requirements and the irradiator operating and
emergency procedures; and
5) Minimum
training and experience of personnel who may provide training.
c) The
application shall include an outline of the written operating and emergency
procedures listed in Section 346.530 of this Part that describe the radiation
safety aspects of the procedures.
d) The
application shall describe the organizational structure for managing the
irradiator, specifically the radiation safety responsibilities and authorities
of the radiation safety officer and those management personnel who have
important radiation safety responsibilities or authorities. In particular, the
application shall specify who, within the management structure, has the
authority to stop unsafe operations. The application shall also describe the
training and experience required for the position of radiation safety officer.
e) The
application shall include a description of the access control systems required
by Section 346.230 of this Part, the radiation monitors required by Section
346.290 of this Part, the method of detecting leaking sources required by
Section 346.590 of this Part, including the sensitivity of the method, and a
diagram of the facility that shows the location of all required interlocks and
radiation monitors.
f) An
application for a panoramic irradiator shall include a description of the
facility shielding and fire protection system.
g) An
application for a pool irradiator shall include a description of the irradiator
pool construction, water level indicators, purification systems and source rack
and protection system.
h) If
the applicant intends to perform leak testing of dry-source-storage sealed
sources, the applicant shall establish procedures for leak testing and submit a
description of these procedures to the Agency. The description shall include
the:
1) Instruments
to be used;
2) Methods
of performing the analysis; and
3) Pertinent
experience of the personnel analyzing the samples.
i) If the
licensee's personnel are to load or unload sources, the applicant shall
describe the qualifications and training of the personnel and the procedures to
be used. If the applicant intends to contract for source loading or unloading
at its facility, the loading or unloading shall be done by an organization
specifically authorized by the Agency, U.S. Nuclear Regulatory Commission or an
Agreement State to load or unload irradiator sources.
j) The
applicant shall describe the inspection and maintenance checks, including the
frequency of the checks required by Section 346.610 of this Part.
k) A professional
engineer licensed in Illinois shall seal all construction and design plans and
specification documents submitted for review by the Agency.
l) Appropriate
Agency license fees, as specified in 32 Ill. Adm. Code 331: Appendix F, shall
be paid prior to the approval of the specific license.