32 Ill. Adm. Code 505.2000
Standards for Design, Construction, Operation and Inspection
Section 505
Section 505.2000 Standards
for Design, Construction, Operation and Inspection
Non-ISI boilers and pressure
vessels, including related appurtenances, except those exempt under Section
505.50(a), operated within or upon or in connection with a nuclear facility in
Illinois, shall be designed, constructed, installed, examined, tested,
repaired, altered and inspected as required by this Section, except in those
cases in which NRC has jurisdiction, as determined by NRC. When NRC has
jurisdiction, the codes and standards reflected in the facility's Operating
License, Final Safety Analysis Report, technical specifications or other
licensing documents as required or approved by the NRC shall apply. For
non-ISI boilers and pressure vessels over which NRC has no jurisdiction, as
determined by NRC, the standards required by this Part apply. If the NRC
determines that NRC has jurisdiction, but has not established standards, the Agency
may propose to NRC that these or other standards be applied to such boilers and
pressure vessels in nuclear power plants in Illinois.
a) All new, existing and reinstalled non-ISI boilers, including
related appurtenances, shall be designed, constructed, installed, examined,
tested, repaired and altered in accordance with the ASME Code or National Board
Inspection Code, as applicable, and inspected in accordance with this Part.
Where a non-ISI boiler is moved and reinstalled, the fittings and appliances of
that boiler shall comply with this Part.
b) All non-ISI pressure vessels installed and placed in operation
after December 31, 1976 and all reinstalled non-ISI pressure vessels, including
related appurtenances, shall be designed, constructed, installed, tested,
examined, repaired and altered in accordance with the ASME Code or National
Board Inspection Code, as applicable, and inspected in accordance with this
Part. Where a non-ISI pressure vessel is moved and reinstalled, the fittings
and appliances of that pressure vessel shall comply with this Part.
c) Non-ISI pressure vessels and related appurtenances installed
and placed in operation at nuclear facilities on or before December 31, 1976
shall be inspected in accordance with this Part and designed, constructed,
installed, tested, repaired and altered, in accordance with the following
requirements.
1) The MAWP for standard pressure vessels shall be determined in
accordance with the applicable provisions of the ASME Code under which they
were constructed and stamped.
2) MAWP for Non-standard Pressure Vessels
A) The MAWP of a non-standard pressure vessel subject to internal
pressure shall be determined by the strength of the weakest course computed
from the thickness of the plate, the tensile strength of the plate, the
efficiency of the longitudinal joint, the inside diameter of the course and the
factor of safety set by this Part, as follows:
TS
x t x E
=
MAWP, in psig
R
x FS
where:
TS
=
ultimate tensile strength of
shell plate, in psi. When the tensile strength of steel plate is not known,
it shall be taken as 55,000 psi for temperature not exceeding 650° F.
t
=
minimum thickness of shell
plate of weakest course, in inches.
E
=
efficiency of longitudinal
joint, depending upon construction. Use the following values (in percents):
For Fusion-Welded and Brazed
Joints:
Single lap welded........................................ 40
Double lap welded....................................... 60
Single butt welded....................................... 60
Double butt welded..................................... 75
Forge welded............................................... 70
Brazed steel................................................. 80
For riveted joints −
calculate riveted joint efficiency in accordance with rules given in Section I,
Part PR, of the 1971 ASME Code.
R
=
inside
radius for weakest shell course, in inches, provided the thickness does not
exceed 10 percent of the radius. If the thickness is over 10 percent of the
radius, the outer radius shall be used.
FS
=
factor of
safety permitted shall be a minimum of 5.0.
B) The MAWP for cylindrical non-standard pressure vessels subject
to external or collapsing pressure shall be determined by the rules in Par.
UG-27 and UG-28 of the ASME Code Section VIII.
C) The minimum factor of safety may be increased when deemed
necessary by the Authorized Inspector to assure the operation of the vessel
within safe limits. The condition of the vessel and the particular service to
which it is subject will be determining factors.
D) The MAWP permitted for formed heads under pressure shall be determined
by using the appropriate formulas from UG-32 or UG-33 of the ASME Code Section
VIII and the tensile strength and efficiencies given in this Section.
d) All non-ISI boilers and pressure vessels, including related
appurtenances, shall be inspected in accordance with the National Board
Inspection Code and this subsection (d). The following general requirements
shall apply to all non-ISI boilers and pressure vessels.
1) The owner shall prepare each boiler and pressure vessel for
internal inspection in accordance with the National Board Inspection Code. The
Authorized Inspector should not enter any boiler or pressure vessel before he or
she is satisfied that all necessary safety precautions of the National Board
Inspection Code have been taken, including testing the boiler or pressure
vessel atmosphere for oxygen and toxic, flammable and inert gases.
2) The owner shall prepare for and apply the hydrostatic test,
whenever necessary, on a date agreeable to the owner and the Authorized
Inspector.
e) All cases not specifically covered by this Part shall be
treated as new installations. Existing non-ISI boilers and pressure vessels
shall be governed by current ASME Code and National Board Inspection Code
requirements or the requirements of the ASME Code in effect at the time of
construction.