35 Ill. Adm. Code 201.630
Nitrogen Oxide (NOx) Requirements
Section
201.630Â Nitrogen Oxide (NO
x
) Requirements
The owner
or operator of the PBR boiler must comply with the following, as applicable:
a)Â Â Â Â Â Â Â Â If the PBR boiler is
subject to the requirements of 35 Ill. Adm. Code 217.Subpart D, comply with all
the applicable requirements of 35 Ill. Adm. Code 217.Subparts D and E;
b)Â Â Â Â Â Â Â Â If the PBR boiler is
subject to the requirements of 40 CFR 63.subpart DDDDD, comply with all
applicable requirements, including the combustion tuning work practice
requirements of 40 CFR 63.7540(a)(10), as incorporated by reference in Section
201.104; and
c)Â Â Â Â Â Â Â Â For a boiler with a
maximum design heat input capacity greater than 50 MMBtu/hr, and not subject to
either 35 Ill. Adm. Code 217.Subpart D or 40 CFR 63, subpart DDDDD, conduct
combustion tuning for the boiler. This tuning must be conducted in each
calendar year in which the boiler is operated, except for the calendar year in
which the boiler first starts up and the calendar year in which the boiler is
permanently removed from service. The combustion tuning must be conducted as
specified by 40 CFR 63.7540(a)(10)(i) through (vi), as incorporated by
reference in Section 201.104, and be conducted while burning the type of fuel
that provided the majority of the heat input to the boiler over the 12 months
prior to the tune-up.