35 Ill. Adm. Code 214.121
Large Sources
Section 214
Section 214.121 Large
Sources
This Section applies to new fuel
combustion emission sources with actual heat input greater than 73.2 MW (250 mmBtu/hr).
a) Solid Fuel Burned Exclusively. No person shall cause or allow
the emission of sulfur dioxide into the atmosphere in any one hour period from
any new fuel combustion emission source greater than 73.2 MW (250 mmBtu/hr),
burning solid fuel exclusively, to exceed 1.86 kg of sulfur dioxide per MW-hr
of actual heat input (1.2 lbs/mmBtu).
(BOARD NOTE:
This Section was invalidated in Commonwealth Edison v. PCB, 25 Ill. App.3d 271,
62 Ill.2d 494, 43 N.E.2d 459, 323 N.E.2d 84, Ashland Chemical Corp. v. PCB, 64
Ill. App.3d 169, and Illinois State Chamber of Commerce v. PCB, 67 Ill. App.3d
839, 384 N.E.2d 922, 78 Ill.2d 1, 398 N.E.2d 9.)
b) Liquid Fuel Burned Exclusively.
1) Prior to January 1, 2017, no person shall cause or allow the
emission of sulfur dioxide into the atmosphere in any one hour period from any
new fuel combustion emission source with actual heat input greater than 73.2 MW
(250 mmBtu/hr), burning liquid fuel exclusively, to exceed the following:
A) 1.2 kg of sulfur dioxide per MW-hr of actual heat input when
residual fuel oil is burned (0.8 lbs/mmBtu); and
B) 0.46 kg of sulfur dioxide per MW-hr of actual heat input when
distillate fuel oil is burned (0.3 lbs/mmBtu);
2) On and after
January 1, 2017, the owner or operator of a new fuel combustion emission source
with actual heat input greater than 73.2 MW (250 mmBtu/hr), burning liquid fuel
exclusively, must comply with the following:
A) The sulfur
content of all residual fuel oil used by the fuel combustion emission source
must not exceed 1000 ppm;
B) The sulfur
content of all distillate fuel oil used by the fuel combustion emission source
must not exceed 15 ppm; and
C) The owner or
operator must:
i) Maintain
records demonstrating that the fuel oil used by the fuel combustion emission
source complies with the requirements in subsections (b)(2)(A) and (b)(2)(B), such
as records from the fuel supplier indicating the sulfur content of the fuel
oil;
ii) Retain the
records for at least 5 years, and provide copies of the records to the Agency
within 30 days after receipt of a request by the Agency; and
iii) Notify the
Agency within 30 days after discovery of deviations from any of the
requirements in this subsection (b)(2). At minimum, and in addition to any
permitting obligations, the notification must include a description of the
deviations, a discussion of the possible cause of the deviations, any
corrective actions taken, and any preventative measures taken.