35 Ill. Adm. Code 215.124
External Floating Roofs
Section 215
Section 215.124 External
Floating Roofs
a) In addition to meeting the requirements of Section 215.123(b),
no owner or operator of a stationary storage tank equipped with an external
floating roof shall cause or allow the storage of any volatile petroleum liquid
in the tank unless:
1) The tank has been fitted with a continuous secondary seal
extending from the floating roof to the tank wall (rim mounted secondary seal)
or any other device which controls volatile organic material emissions with an
effectiveness equal to or greater than a rimmounted secondary seal;
2) Each seal closure device meets the following requirements:
A) The seal is intact and uniformly in place around the
circumference of the floating roof between the floating roof and tank wall; and
B) The accumulated area of gaps exceeding 0.32 centimeter (1/8
inch) in width between the secondary seal and the tank wall shall not exceed
21.2 square centimeters per meter of tank diameter (1.0 square inches per foot
of tank diameter).
3) Emergency roof drains are provided with slotted membrane
fabric covers or equivalent covers across at least 90 percent of the area of
the opening;
4) Openings are equipped with projections into the tank which
remain below the liquid surface at all times;
5) Inspections are conducted prior to May 1 of each year to
insure compliance with subsection (a);
6) The secondary seal gap is measured prior to May 1 of each
year;
7) Records of the types of volatile petroleum liquid stored, the
maximum true vapor pressure of the liquid as stored, the results of the
inspections and the results of the secondary seal gap measurements are
maintained and available to the Agency, upon verbal or written request, at any
reasonable time for a minimum of two years after the date on which the record
was made.
b) Subsection (a) does not apply to any stationary storage tank
equipped with an external floating roof:
1) Exempted under Section 215.123(a)(2) through 215.123(a)(6);
2) Of welded construction equipped with a metallic-type shoe seal
having a secondary seal from the top of the shoe seal to the tank wall
(shoe-mounted secondary seal);
3) Of welded construction equipped with a metallic-type shoe
seal, a liquid-mounted foam seal, or a liquid-mounted liquid-filled-type seal,
or other closure device of equivalent control efficiency approved by the Agency
in which a petroleum liquid with a true vapor pressure less than 27.6 kPa (4.0
psia) at 294.3º K (70º F) is stored; or
4) Used to store crude oil.