35 Ill. Adm. Code 215.581
Bulk Gasoline Plants
Section 215
Section 215.581 Bulk
Gasoline Plants
a) Subject to subsection (e), no person may cause or allow the
transfer of gasoline from a delivery vessel into a stationary storage tank
located at a bulk gasoline plant unless:
1) The delivery vessel and the stationary storage tank are each
equipped with a vapor collection system that meets the requirements of
subsection (d)(4);
2) Each vapor collection system is operating;
3) The delivery vessel displays the appropriate sticker pursuant
to the requirements of Section 215.584(b) or (d);
4) The pressure relief valve(s) on the stationary storage tank
and the delivery vessel are set to release at no less than 0.7 psi or the
highest pressure allowed by state or local fire codes or the guidelines of the
National Fire Prevention Association; and
5) The stationary storage tank is equipped with a submerged
loading pipe.
b) Subject to subsection (f), no person may cause or allow the
transfer of gasoline from a stationary storage tank located at a bulk gasoline
plant into a delivery vessel unless:
1) The requirements set forth in subsections (a)(1) through
(a)(4) are met; and
2) Equipment is available at the bulk gasoline plant to provide
for the submerged filling of the delivery vessel or the delivery vessel is
equipped for bottom loading.
c) Subject to subsection (e), each owner of a stationary storage
tank located at a bulk gasoline plant shall:
1) Equip each stationary storage tank with a vapor control system
that meets the requirements of subsection (a) or (b), whichever is applicable;
2) Provide instructions to the operator of the bulk gasoline
plant describing necessary maintenance operations and procedures for prompt
notification of the owner in case of any malfunction of a vapor control system;
and
3) Repair, replace or modify any worn out or malfunctioning
component or element of design.
d) Subject to subsection (e), each operator of a bulk gasoline
plant shall:
1) Maintain and operate each vapor control system in accordance
with the owner's instructions;
2) Promptly notify the owner of any scheduled maintenance or
malfunction requiring replacement or repair of a major component of a vapor
control system; and
3) Maintain gauges, meters or other specified testing devices in
proper working order;
4) Operate the bulk plant vapor collection system and gasoline
loading equipment in a manner that prevents:
A) Gauge pressure from exceeding 18 inches of water and vacuum
from exceeding 6 inches of water, as measured as close as possible to the vapor
hose connection; and
B) A reading equal to or greater than 100 percent of the lower
explosive limit (LEL measured as propane) when tested in accordance with the
procedure described in EPA 450/2-78-051 Appendix B; and
C) Avoidable leaks of liquid during loading or unloading
operations.
5) Provide a pressure tap or equivalent on the bulk plant vapor
collection system in order to allow the determination of compliance with
215.581(d)(4)(A); and
6) Within 15 business days after discovery of the leak by the
owner, operator, or the Agency, repair and retest a vapor collection system
which exceeds the limits of subsection (d)(4)(A) or (B).
e) The requirements of subsection (a), (c) and (d) shall not apply
to:
1) Any stationary storage tank with a capacity of less than 575
gallons; or
2) Any bulk gasoline plant whose annual gasoline throughput is
less than 350,000 gallons as averaged over the preceding three calendar years.
f) The requirements of subsection (b) shall only apply to bulk
gasoline plants:
1) That have an annual gasoline throughput greater than or equal
to 1,000,000 gallons, as averaged over the preceding three calendar years; and
2) That either distribute gasoline to gasoline dispensing
facilities subject to the requirements of Section 215.583(a)(2), 35 Ill. Adm.
Code 218.583(b)(2) or 35 Ill. Adm. Code 219.583(a)(2) or that are located in
the following counties: Boone, Peoria, Rock Island, Tazewell or Winnebago.
g) Bulk gasoline plants were required to take certain actions to