35 Ill. Adm. Code 215.583
Gasoline Dispensing Facilities - Storage Tank Filling Operations
Section 215
Section 215.583 Gasoline
Dispensing Facilities - Storage Tank Filling Operations
a) Subject to subsection (b) below, no person shall cause or
allow the transfer of gasoline from any delivery vessel into any stationary
storage tank at a gasoline dispensing facility unless:
1) The tank is equipped with a submerged loading pipe; and
2) The vapors displaced from the storage tank during filling are
processed by a vapor control system that includes one or more of the following:
A) A vapor collection system that meets the requirements of
subsection (d)(4) below; or
B) A refrigeration-condensation system or any other system
approved by the Agency that recovers at least 90 percent by weight of all
vaporized organic material from the equipment being controlled; and
C) The delivery vessel displays the appropriate sticker pursuant
to the requirements of Section 215.584(b) or (d) of this Part.
b) The requirements of subsection (a)(2) above shall not apply to
transfers of gasoline to a stationary storage tank at a gasoline dispensing
facility if:
1) The tank is equipped with a floating roof or other system of
equal or better emission control as approved by the Agency;
2) The tank has a capacity of less than 2000 gallons and is in
place and operating before January 1, 1979;
3) The tank has a capacity of less than 575 gallons; or
4) The tank is not located in any of the following counties:
Boone, Cook, DuPage, Kane, Lake, Madison, McHenry, Peoria, Rock Island, St.
Clair, Tazewell, Will or Winnebago.
c) Subject to subsection (b) above, each owner of a gasoline
dispensing facility shall:
1) Install all control systems and make all process modifications
required by subsection (a) above;
2) Provide instructions to the operator of the gasoline
dispensing facility describing necessary maintenance operations and procedures
for prompt notification of the owner in the case of any malfunction of a vapor
control system; and
3) Repair, replace or modify any worn out or malfunctioning
component or element of design.
d) Subject to subsection (b) above, each operator of a gasoline
dispensing facility and each delivery vessel operator shall:
1) Maintain and operate each vapor control system in accordance
with the owner's instructions;
2) Promptly notify the owner of any scheduled maintenance or
malfunction requiring replacement or repair of a major component of a vapor
control system;
3) Maintain gauges, meters or other specified testing devices in
proper working order;
4) Operate the vapor collection system and delivery vessel unloading
points in a manner that prevents:
A) A reading equal to or greater than 100 percent of the lower
explosive limit (LEL measured as propane) when tested in accordance with the
procedure described in EPA 450/2-78-051 Appendix B, and
B) Avoidable leaks of liquid during the filling of storage tanks;
and
5) Within 15 business days after discovery of the leak by the
owner, operator, or the Agency, repair and retest a vapor collection system
which exceeds the limits of subsection (d)(4)(A) above.
e) Gasoline dispensing facilities were required to take certain
actions to achieve compliance which are summarized in Appendix C of this Part.