35 Ill. Adm. Code 217.164
Emissions Limitations
Section 217.164 Emissions Limitations
a) Except
as provided for under Section 217.152, on and after January 1, 2015, no person
shall cause or allow emissions of NO
x
into the atmosphere from any
industrial boiler to exceed the following limitations. Until July 1, 2025,
compliance must be demonstrated with the applicable emissions limitation on an
ozone season and annual basis. On and after July 1, 2025, compliance must be
demonstrated with the applicable emissions limitation on a 30-day rolling
average basis.
Fuel
Emission
Unit Type and Rated Heat Input Capacity (mmBtu/hr)
NO
x
Emissions Limitation (lb/mmBtu) or Requirement Before July 1, 2025
Natural Gas
or Other Gaseous Fuels
Industrial boiler greater than
100
0.08
Industrial boiler less than or
equal to 100
Combustion tuning
Distillate
Fuel Oil
Industrial boiler greater than
100
0.10
Industrial boiler less than or
equal to 100
Combustion tuning
Other Liquid
Fuels
Industrial boiler greater than
100
0.15
Industrial boiler less than or
equal to 100
Combustion tuning
Solid Fuel
Industrial boiler greater than
100, circulating fluidized bed combustor
0.12
Industrial boiler greater than
250
0.18
Industrial boiler greater than
100 but less than or equal to 250
0.25
Industrial boiler less than or
equal to 100
Combustion tuning
Fuel
NO
x
Emission Unit Type and Rated Heat Input Capacity (mmBtu/hr)
Limitation
(lb/mmBtu) or Requirement
On
and after July 1, 2025
Natural Gas or Other Gaseous
Fuels
Industrial boiler greater than
50
0.08
Industrial boiler less than or
equal to 50
Combustion tuning
Distillate Fuel
Oil
Industrial boiler greater than 50
0.10
Industrial boiler less than or
equal to 50
Combustion tuning
Other Liquid Fuels
Industrial boiler greater than 50
0.15
Industrial boiler less than or
equal to 50
Combustion tuning
Solid Fuel
Industrial boiler greater than 50,
circulating fluidized bed combustor
0.10
Industrial boiler greater than
250
0.15
Industrial boiler greater than 50
but less than or equal to 250
0.20
Industrial boiler less than or
equal to 50
Combustion tuning
b) For
an industrial boiler combusting a combination of natural gas, coke oven gas,
and blast furnace gas, the NO
x
emissions limitation must be
calculated using the following equation:
NO
x
emissions limitation
for period in lb/mmBtu
=
Where:
=
0.084 lb/mmBtu for natural gas
=
the heat inpu of natural gas
in Btu over that period
=
0.144 lb/mmBtu for coke oven gas
=
the heat input of coke oven gas in Btu over that period
=
0.0288 lb/mmBtu for blast furnace gas
=
the heat input of blast furnace gas in Btu over that
period